Fire Alarm Systems | D9124 Addressable Fire Alarm Control Panel (FACP)

The D9124 FACP controls complex alarm systems used in
schools, universities, manufacturing plants, and health care
facilities. Program it for fire, fire supervisory, intrusion, or
access control applications. Program it locally using the
D5200CE hand-held programmer or remotely using RPS
over telephone lines or local-area or wide-area networks
(LAN or WAN).
The D9124 FACP is a modular assembly, installed in a red
steel enclosure, which can be surface- or flush-mounted.
The enclosure has keyed controller access making it
suitable for installation in public access areas.

Functions

Alarm Verification
The alarm verification feature reduces potential false alarms
by requiring a reset and a second alarm signal from the
device before the control panel raises an alarm condition.
Auxiliary and Standby Power
The 4 A, 24 VDC power supply charges the standby batteries
and powers auxiliary devices. The power supply responds
to low battery or battery disconnect conditions with a
Trouble LED and a Trouble Relay for sounders or lights.

Five system power trouble conditions are selected by DIP
switches. They can be individually linked to a central
station, or grouped to activate a trouble relay, allowing a
single supervised address to monitor the power supply.
A pair of 12 V batteries provides standby power. Two
additional batteries provide standby power for initiating
devices and notification appliances. All four batteries are
housed within the panel enclosure.

Note

Batteries are not included in the D9124 and
must be purchased separately.

Central Station Communication
Events can be communicated to a central station by the
digital communicator or by adding an optional Ethernet
interface module. The optional Bosch D6500 or D6600
NetCom Receiver and Modem IIIa

2

 reporting format provide

individual point reporting to monitoring facilities.
The D5500 Remote Programming Software (RPS) allows
the following to be controlled from a central station:

Resetting notification appliances

Activating or deactivating remote annunciation

Activating or deactivating relays

Supervising battery condition

Setting point status and armed status

Enabling or disabling reporting functions

Shunting reporting points during servicing

D9124 Addressable Fire Alarm Control

Panel (FACP)

24 VDC, 4 A power for initiation circuits and NACs;

12 VDC, 1.4 A power for system accessories

Up to eight supervised or 32 unsupervised remote

annunciators

One-man Fire Test Mode

Schedules (Skeds function) service reminder for local

systems

Low battery, AC power supply, and battery lead

supervision

Dual phone line monitor

www.boschsecurity.com

Summary of Contents for D9124

Page 1: ...te a trouble relay allowing a single supervised address to monitor the power supply A pair of 12 V batteries provides standby power Two additional batteries provide standby power for initiating devices and notification appliances All four batteries are housed within the panel enclosure Note Batteries are not included in the D9124 and must be purchased separately Central Station Communication Event...

Page 2: ...liance Circuits NACs The D9124 FACP has two supervised on board NACs with individual circuit silencing User Interface A D1256 Fire Alarm keypad is visible and accessible behind a locked clear sliding panel located on the enclosure door It displays programmable text identifying specific initiating and supervisory devices It also provides point annunciation signal silence trouble silence detector re...

Page 3: ...d 1 Literature pack Technical Specifications Environmental Considerations Relative Humidity Up to 85 non condensing Temperature operating 32 F to 122 F 0 C to 50 C Inputs Sensor Circuits Up to two 8125 POPEX modules 119 addresses per module Sensor Circuit Protection Power limited to 4 A short circuit reverse polarity thermal overload and current over load protection on board Sensor Loop Technology...

Page 4: ... Inc 130 Perinton Parkway Fairport New York 14450 USA Phone 1 800 289 0096 Fax 1 585 223 9180 security sales us bosch com www boschsecurity us Europe Middle East Africa Bosch Security Systems B V P O Box 80002 5600 JB Eindhoven The Netherlands Phone 31 40 2577 284 Fax 31 40 2577 330 emea securitysystems bosch com www boschsecurity com Asia Pacific Robert Bosch SEA Pte Ltd Security Systems 11 Bisha...

Reviews: