![Bosch D296 Series Installation Manual Download Page 25](http://html.mh-extra.com/html/bosch/d296-series/d296-series_installation-manual_50446025.webp)
Long-range beam smoke detectors
Troubleshooting | en
25
Bosch Security Systems, Inc.
Installation manual
2017.03 | 7.0 | F.01U.068.899
7
Troubleshooting
7.1
Transmitter
LED
Condition
Solution
Flashing
Normal
Off
1. There is no power at the transmitter.
2. The Aim Mode button not pressed.
3. The transmitter is faulty.
1. Restore power to Terminals 1 and 2.
2. Press the Aim Mode button.
3. Replace the transmitter.
7.2
Receiver - Aim Mode (cover off)
Red
LED
Yellow
LED
Green
LED
Terminals 4
and 5
Terminals 6
and 7
Condition
Solution
On
On
Flashing
Open
Open
The alignment is
acceptable.
On
On
On
Open
Open
The beam is
blocked or the
receiver is
misaligned.
Clear the beam
path or realign
the receiver.
On
Flashing
Flashing
Open
Open
The sensitivity
setting is invalid.
Set the receiver
to the proper
setting.
On
Off
Off
Open
Open
There is no power.
Check for power
at Terminals 8
and 9.
7.3
Receiver - Normal Mode (cover on)
Red
LED
Yellow
LED
Green
LED
Terminals 4
and 5
Terminals 6
and 7
Condition
Solution
Off
Off
On
Open
Closed
The receiver is
initializing. It
stabilizes in 60 sec to
120 sec.
Off
Off
On
Open
Open
The receiver is
initializing. The
access door is
missing or loose.
Replace the
access door.
Off
Off
Flashing
Open
Closed
Normal
Off
Off
Flashing
Open
Open
The access door is
missing or loose.
Replace the
access door.
Off
On
On
Open
Open
Trouble. Beam is
blocked or
misaligned.
Clear the beam
path or realign
the receiver.