Installation
Greenstar FS/Combi FS – 6 720 810 590 (2020/04)
36
6.7
Locating the appliance
NOTICE:
Residue, metal shavings, and contaminants in the piping can
damage the appliance.
▶ Flush the piping thoroughly and completely to remove all residue.
▶ Follow the instructions with respect to water quality (
Section ).
▶ Remove packaging, observing all notes and symbols.
▶ On the rating plate, check the identification of the target country and
suitability for the gas type supplied by the local gas utility company
(
fig. 74).
Removing the cover:
To remove the cover:
▶ Pull the front panel towards you from the top right and left edge to
release the ball catches [1] from their retainers [2]
▶ Lift the front panel off the lower mounts [3] and place in a safe
location away from the work area
Fig. 21 Remove the cover
6.7.1
Positioning the appliance
The boiler must be adjusted to be level. This ensures air can escape from
the heat exchanger and condensate drains freely.
NOTICE:
Damage caused by insufficient load bearing or unsuitability of the
boiler room floor
▶ Ensure the floor area is suitable for installing a boiler and can take the
“wet weight” of the appliance.
NOTICE:
Damaged caused by mechanical strain on the hydraulic and flue gas
connections when adjusting the position of the appliance.
▶ Do not apply any strain the connections when adjusting the boiler
position
▶ Place boiler in its final location
▶ Release the locknuts on the boiler feet .
▶ Adjust the boiler feet until the boiler is level vertically and
horizontally, check using a spirit level
▶ Secure in position with the locknuts
Fig. 22 Levelling the boiler
6.8
Installing a Low Water Cut off (LWCO)
The boiler is equipped with a dedicated port for installation of a LWCO
device on the supply pipe on the back of the boiler cabinet. This location
represents the minimum water level for safe operation of the boiler.
The LWCO device must be specified for an ambient temperature of
176°F (80 °C) and a water temperature of 250 °F (121 °C).
The following LWCO is approved with the boiler:
• Hydrolevel Safgard 1100
The device is available at most Bosch wholesalers. It requires an external
24VAC minimum 20VA transformer provided on site.
If other LWCO devices are to be used, they must be installed externally to
the boiler.
6720810590-12.1W
o
1
2
3
6720809859-79.2W
o