4-6
Climate Class 6100i / 6000i / 8100i / 8000i
[4] HOW TO OPERATE THE OUTDOOR UNIT INDEPENDENTLY
1.Cooling in 40 Hz fixed mode
To operate the outdoor unit independently, short-circuit the sections indicated by arrows in the diagram below with an adapter, and apply 230 VAC
between (1) and (N) on the terminal board of the outdoor unit. This allows the outdoor unit to be operated in cooling mode independently.
(Do not operate the outdoor unit in this condition for an extended period of time.)
L3
L2
If these pads are connected and Power is applied to N and 1 on terminal board.
Then the outdoor unit operate in "TEST COOL 40Hz" mode.
Soldering Side
C5
C6
[5] GENERAL TROUBLESHOOTING CHART
* These models have following thermistors
INDOOR UNIT
OUTDOOR UNIT
TH1, TH2
TH1, TH2, TH3, TH4, TH5
The errors for the thermistors that are not mentioned above are irrelevant.
These indoor units don’t have power relay.
1.Indoor unit does not turn on
Main cause
Inspection method
Normal value/condition
Remedy
Cracked PWB.
(Cracked pattern)
Check visually.
There should be no cracking in
PWB or pattern.
Replace PWB.
Open-circuit in FU1
(250 V, 3.15 A)
Check melting of FU1.
There should be no open-cir-
cuit.
Replace PWB.
2.Indoor unit fan does not operate
Main cause
Inspection method
Normal value/condition
Remedy
Open-circuit in heat exchanger
thermistor (TH2) (in heating opera-
tion)
Measure thermistor resistance
(dismount for check).
Refer to THERMISTOR TEM-
PERATURE CHARACTERIS-
TICS-1
Replace thermistor.
There should be no open-cir-
cuit or faulty contact.
Replace thermistor.
Disconnected heat exchanger therm-
istor (TH2) (in heating operation)
Inspect connector on PWB.
Check thermistor installation
condition.
Thermistor should not be dis-
connected.
Install correctly.
3.Indoor unit fan speed does not change
Main cause
Inspection method
Normal value/condition
Remedy
Remote control not designed to allow
fan speed change.
Check operation mode.
Fan speed should change
except during dehumidifying
operation, ventilation, light de-
humidifying operation, internal-
ly normal operation
Explain to user.
4.Remote control signal is not received
Main cause
Inspection method
Normal value/condition
Remedy
Batteries at end of service life.
Measure battery voltage.
2.5 V or higher (two batteries in
series connection)
Install new batteries.
Batteries installed incorrectly.
Check battery direction.
As indicated on battery com-
partment.
Install batteries in indicated
direction.
Lighting fixture is too close, or fluo
-
rescent lamp is burning out.
Turn off light and check.
Signal should be received
when light is turned off.
Change light position or install
new fluorescent lamp.
Summary of Contents for CLC6001i 25 E
Page 69: ...2 Climate Class 6100i 6000i 8100i 8000i 6 1 6 3 6 4 6 2 ...
Page 77: ...10 Climate Class 6100i 6000i 8100i 8000i 6 1 6 3 6 4 6 2 ...
Page 87: ...20 Climate Class 6100i 6000i 8100i 8000i 7 28 Reverse Value Ass y ...
Page 88: ...21 Climate Class 6100i 6000i 8100i 8000i Expansion Value Ass y ...