Heating circuit data
|
25
6 720 802 836 (2012/05)
CFB 840
10.2 Rename the heating circuit
Instead of the designation
Heat.circuit
+ No. another name can be
selected from a list provided.
B
Call up the service level.
GENERAL PARAM.
appears as the first main menu.
B
Turn the rotary dial until main menu
Heat.circuit
+ No. is displayed.
B
Press
Display
to call up a submenu.
B
Turn the rotary dial until submenu
Heating circ. desig.
appears.
Fig. 27 Rename the heating circuit
B
Hold down button
Display
and turn the rotary dial until the required
value is shown.
B
Release
Display
to save your input.
B
Press
Back
to return to the next higher level.
10.3 Setting the low end temperature
This function will only be displayed for "Low end" heating systems.
By setting
the heating system to Low end,
the system is set to a straight
heating curve using the low end and design temperatures.
The base point [Low end] temperature determines the start of the
heating curve. The low end temperature is applicable for an outside
temperature of 20 °C.
B
Call up the service level.
GENERAL PARAM.
appears as the first main menu.
B
Turn the rotary dial until main menu
Heat.circuit
+ No. is displayed.
B
Press
Display
to call up a submenu.
B
Turn the rotary dial until submenu
Heating system
appears.
B
Hold down button
Display
and turn the rotary dial until the required
value is shown.
B
Release
Display
to save your input.
B
Turn the rotary dial until submenu
Base point temp.
appears.
B
Hold down button
Display
and turn the rotary dial until the required
value is shown.
Fig. 28 Setting the low end temperature
B
Release
Display
to save your input.
B
Press
Back
to return to the next higher level.
10.4 Setting the design temperature
The design temperature is the flow temperature at the adjusted
minimum outside temperature.
For the heating system
Low end
the following applies:
•
Set the design temperature at least 10 °C higher than the low end
temperature.
•
Changing the design temperature allows the heating system to
operate with a flatter or steeper heating curve.
B
Call up the service level.
GENERAL PARAM.
appears as the first main menu.
B
Turn the rotary dial until main menu
Heat.circuit
+ No. is displayed.
B
Press
Display
to call up a submenu.
B
Turn the rotary dial until submenu
Design temp.
appears.
B
Hold down button
Display
and turn the rotary dial until the required
value is shown.
Fig. 29 Setting the design temperature
B
Release
Display
to save your input.
B
Press
Back
to return to the next higher level.
Input range
Factory setting
Heating system
none
Radiator
Convector
Underfloor
Constant
Low end
Room controller
Radiator
Table 38 Setting range Heating system
Input range
Factory setting
Heat circ. desig
Heating circ.
Apartment
Underfloor
Bathroom
Swimming pool
Floor
Cellar
Building
Heating circ.
Table 39 Setting range Heating circuit name
HEAT CIRC. DATA 2
Heat circ desig.
Heating circ.
6 720 802 836-41.1TL
Input range
Factory setting
Base point temp.
20 °C – 80 °C
30 °C
Table 40 Setting range Low end temperature
Observe the information regarding setting the heating
curves.
HEAT CIRC. DATA 2
Base point temp.
32
6 720 802 836-42.1TL
C
o
HEAT CIRC. DATA 2
Design temp.
65
6 720 802 836-43.1TL
C
o