Conettix Universal Dual Path Communicator
Installation | en
19
Bosch Security Systems, Inc.
Installation and Operation Manual
2017.11 | 05 | F.01U.311.207
4.7
Wiring installation
Refer to the following sections for detailed wiring information.
4.7.1
System wiring
You can use the B465 with a variety of intrusion and fire control panels that support the
B465’s compatible protocols.
T
MPR
BAT
ET
HERNET
EXT
ERNAL
ANNUNC
X
MODULE 1
Y
MODULE
RELEASE
1 COM 2
3 COM 4
T R
PNL LINE 1
C NO
RELAY 2
16.5VAC
NC C NO
RELAY 1
TRBL
TX
RX
PWR
PANEL
LINE 2
USB
ETHERNET
100BASE-T
LINK
COMMUNICATION MODULE 1
3 COM 4
1 COM 2
R Y G
B
SDI2
Device Bus
BATTERY
PANEL
LINE 1
BATTERY
POWER
RX
TX
SYSTEM TROUBLE
INPUTS
2.2 k End of
Line Resistors
C NO
RELAY 3
12V
AUX COM
T R
PNL LINE 2
24 VDC
or
16.5 VAC
5
4
6
7
8
9
10
1
2
+ _
+
-
BATTERY
3
11
Figure
4.3: System wiring
Callout
ー
Description
Callout
ー
Description
1
ー
RJ-45 modular jack for Ethernet IP
communications (optional)
7
ー
Programmable output relays (Relay 1,
Relay 2, Relay 3)
2
ー
Connector for External Annunciator
(connected to optional B46)
8
ー
12 VDC lead-acid battery (7 to 18 Ah)
3
ー
To tamper switch
9
ー
To earth ground
4
ー
Phone Line 1/2 (to control panel
terminals if required)
10
ー
D1640 plug-in transformer, D1640-CA
plug-in transformer, D1640-120WI wired-in
transformer or optional 24 VDC from a UL
listed fire control panel or power supply
5
ー
Four EOL input loops
11
ー
SDI2 device bus connector (for future
use)
6
ー
12V AUX/COM terminals for 12 VDC
auxiliary power (optional output power
source, Special Application 9.9 to 13.8 V)