Conettix Ethernet Communication Module
Configuration | en
25
Bosch Security Systems, Inc.
Installation and Operation Guide
2016.08 | 08 | F.01U.266.226
Web Access Enable
Default:
No for B6512/B5512/B4512/B3512 and GV4 v2.xx or higher control panels, Yes for all
other control panels
Selections:
Yes, No
Yes:
Web configuration is enabled
No:
Web configuration is disabled
Enable or disable access to the configuration web pages.
Do NOT disable web access unless you are on a SDI2 panel and AMAX 2100/ 3000/ 4000 with
Panel Programming Enable enabled. With SDI and option control panels, the module can only
be configured via the web interface.
Panel Programming Enable
Default:
Yes
Selections:
Yes, No
Yes:
Control panel programming is enabled.
No:
Control panel programming is disabled.
Enable or disable control panel programming of the module with compatible (SDI2-only)
control panels and AMAX 2100/ 3000/ 4000.
Do not disable Web Access Enable and Panel Programming Enable. If both are disabled, you
cannot configure the module.
Firmware Upgrade Enable
Default:
No
Selections:
Yes, No
Yes:
Allows firmware upgrades to the B426.
No:
Prevents firmware upgrades.
Enable or disable the ability to upgrade the module's firmware from the
Firmware Upgrade
configuration page.
Module Hostname
Default:
Blank
Selections:
Sixty-four alphanumeric characters
Blank:
Blank restores the default hostname Bxxxxxx, where as xxxxxx is the last six digits of
the module's MAC address.
Use this parameter to create or change a module hostname. This is the hostname that
represents the module on the network. Optionally use the hostname to contact the control
panel via RPS over network, for Remote Security Control, or for module web configuration and
diagnostics.
Notice!
Use the hostname on a local network using DHCP . To use the hostname externally, enter the
hostname in the DNS server.
Unit Description