The fire panel is easily adapted to local requirements and regulations. Due to the different
functional modules, country-specific characteristics are accommodated in the connection just
as quickly as the respective alarm protocol.
With evacuation button and evacuation zone monitoring the panel achieves full safety panel
functionality.

2.1

Product description

The fire panel allows mixed operation of analog addressable and conventional technology. It
supports connecting periphery in either stub or loop topologies. Analog addressable fire
detectors, manual call points, signaling devices, inputs and outputs are identified and
managed by the fire panel as single elements. As required by the building structure the
peripherals are grouped software wise in logical zones.
AVENAR panel 8000 uses functional modules that are clicked in a slot on a rail.
AVENAR panel 2000 comes as a kit in a housing. The functional modules can be plugged onto
the rail inside the housing.
The rail provides power and internal communication to the functional modules. A wide range
of functional modules are available providing: addressable loops, conventional zones, inputs
and outputs, and interfaces to various devices.
AVENAR panel 8000 can be equipped with 46 functional modules, of which a maximum of 32
can be analog addressable loop modules. This results in a tailor-made fire panel suitable for
medium to large size applications.
AVENAR panel 2000 can be equipped with six functional modules of which a maximum of four
can be analog addressable loop modules. This makes the fire panel suitable for small to
medium size applications.
Two different types of housings are available to assemble the fire panel:

Wall mount housing

Frame mount housing

The slim wall mount housings are for mounting directly to the wall. Frame mount housings
require an additional frame between the housing and the wall. The frame lets space for e.g.
cabling, media converters, and larger batteries. Special installation kits also allow installation
in 19" racks.
The panel controller is the central component of the fire panel. A color display shows all
messages. The touch screen is for operation of the entire system. The user-friendly interface
adapts to various situations. This causes correct operation that is simple and clear as well as
targeted and intuitive.
For AVENAR panel 8000 both housing types can be extended with up-to four housings to
increase the number slots for the functional modules.
Panels and keypads of the AVENAR series and of the FPA-5000 series (MPC-xxxx-B and MPC-
xxxx-C) can be combined in one panel network using the Ethernet and the CAN bus interfaces.
The remote keypad is for decentralized operation of the panel or of the panel network.
Integration into large-scale systems can be done by an Ethernet interface to the Bosch
Hierarchy panel (UGM) or to Building Integration System (BIS). Integration into third party
management systems is possible with the availability of OPC server and Software
Development Kit.
A data interface enables monitoring and full control of Bosch voice alarm systems. This makes
the fire panel a complete safety solution.

Summary of Contents for AVENAR panel

Page 1: ...AVENAR panel en System manual ...

Page 2: ......

Page 3: ...BCM 0000 B modules 40 3 10 Protective earth and equipotential bonding 44 4 Installation 45 4 1 General information 45 4 2 Installation sequence 46 4 3 Installation of CPH 0006 A fully assembled panel 47 4 4 Installation of HCP 0006 A fully assembled panel 48 4 5 Extended line monitoring VdS 2540 VdS 2543 48 4 6 FPP 5000 External Power Supply Unit Kit 24 V 6 A 49 5 Commissioning 51 5 1 Functional t...

Page 4: ...s 66 8 3 Additional documentation 67 8 3 1 Frame installation housings mounting frames and installation kits 67 8 3 2 Wall mounting housings and installation kits 68 8 3 3 Accessories for housing 68 8 3 4 Panel rails 69 8 3 5 Power supply units 69 8 3 6 Panel controller remote keypad 69 8 3 7 Functional modules 70 8 3 8 Cable sets 70 Index 71 ...

Page 5: ... objects e g screw drivers pens etc when operating the touch sensitive display The touchscreen may not be exposed to direct sunlight Both can seriously damage the touchscreen Caution EN 62368 1 MS 3 The installation height is recommended to a maximum of 2 m i Notice Have maintenance and inspection work carried out regularly by trained qualified personnel Bosch recommends a functional and visual in...

Page 6: ...6 en Safety AVENAR panel 2022 07 5 0 F 01U 378 910 System manual Bosch Sicherheitssysteme GmbH i Notice Consider national and local regulations when installling and operating the fire system ...

Page 7: ...applications AVENAR panel 2000 can be equipped with six functional modules of which a maximum of four can be analog addressable loop modules This makes the fire panel suitable for small to medium size applications Two different types of housings are available to assemble the fire panel Wall mount housing Frame mount housing The slim wall mount housings are for mounting directly to the wall Frame m...

Page 8: ...te alarms and events 8 touch pad with fixed and programmable buttons thus adaptable to the situation Integrated Ethernet switch for networking and interfaces to remote services building management and voice alarm systems Adaptable to local requirements and regulations System overview N I T U O A U X 3 A U X A U X 2 A U X A U X 5 A U X 6 B M0 N I T U O L S N 0 3 0 0 A AU X 1 L S N 1 a b AU X 2 L S ...

Page 9: ...ypad of FPA series Each panel controller contains a hard coded software license The licenses define the maximum panel network size and availability of certain features and interfaces In principle the standard license provides basic fire detection features according the standards In addition the premium license provides interfaces for Building management system OPC FSM 5000 FSI Hierarchy panel UGM ...

Page 10: ...stems IOP 0008 A Input output module Individual displays or flexible connection of various electrical devices with 8 independent digital inputs and 8 open collector outputs IOS 0020 A Communication module 20mA With S20 and RS232 interfaces IOS 0232 A Communication module RS232 Connection of two devices using two independent serial interfaces e g Plena or a printer LSN 0300 A LSN bus module 300mA C...

Page 11: ...uction and cannot be modified revoked or transported The license defines the maximum panel network size and availability of certain features and interfaces In total 4 different licenses are available AVENAR panel 2000 standard license AVENAR panel 2000 premium license AVENAR panel 8000 standard license AVENAR panel 8000 premium license Ethernet interface to Building management system BIS FSM 5000 ...

Page 12: ...panels of the network in the hierarchy panel i Notice Voice alarm system connected to AVENAR panel Each fire panel which is physically connected to a voice alarm system via Smart Safety Link needs a premium license i Notice AVENAR panel 2000 networking For each AVENAR panel 2000 which needs to be networked with other panels a premium license is required It is not sufficient to equip only one AVENA...

Page 13: ...y all messages or you can form a group of panels and keypads Within one group only messages of this group are displayed Alarm indication All messages are shown on the display with a bright color The displayed messages contain the following information Message type Type of the triggering element Description of the exact location of the triggering element Logical zone and sub address of the triggeri...

Page 14: ... level of data protection The Ethernet interface provides up to 244 freely configurable virtual VAS triggers The Plena VAS uses an RS232 interface of the IOS 0020 A or IOS 0232 A communication module The Plena VAS can be configured with up to 120 virtual VAS triggers Operator management The system can have up to 200 different registered operators Login is permitted with a user ID and an 8 digit pi...

Page 15: ...eps incoming alarms and events internally The history log has a capacity to store 10000 messages The messages can be shown on the display and you can export the messages Additionally you can connect a log printer via a serial interface module for real time printing incoming messages Installation Refer to the Installation guide for FPE 8000 SPC FPE 8000 PPC FPE 2000 SPC FPE 2000 PPC panel controlle...

Page 16: ... for maintenance services E Power button Shutdown and restart of the device F Product label Important product data G DIP switch label DIP switch label with areas to write down the PNA Physical Node Address and the IP address H Power supply DC1 DC2 I 6 pin DIP switch DIP switch settings for CAN bus networking panel redundancy J 18 LEDs Indicating the operating status It comes with easy to install h...

Page 17: ...allation kits 12 V 45 Ah batteries can be used in the frame installation housing The modular system makes it easy to extend the system Housing Designs and Combinations Two frame installation housings are available as a base unit CPH 0006 A for 6 modules or MPH 0010 A for 10 modules These housings can accommodate a panel controller with an operating and display unit The CPH 0006 A and MPH 0010 A ba...

Page 18: ...s For the FMH 0000 A the FPO 5000 EB Earth Bar can be ordered as an extension if required For continuous installation in combination all mounting frames have T shaped guide rails on the base and T shaped grooves on the top Mounting Plate An HMP 0003 A Mounting plate can be mounted in large mounting frames FBH 0000 A and FHS 0000 A this mounting plate can be individually equipped It contains fixing...

Page 19: ... FRB 0019 A EPH 0012 A FRB 0019 A PSF 0002 A FRB 0019 A PMF 0004 A FRM 0019 A USF 0000 A FRS 0019 A No mounting frame is required when using the 482 6 mm installation kits Scope of Delivery Housing type Scope of delivery each x 1 CPH 0006 A Housing painted sheet steel Power supply bracket Sheet steel front panel with plastic cover Accessories pack with installation material MPH 0010 A Housing pain...

Page 20: ...HCP 0006 A for 6 modules and HBC 0010 A for 10 modules These housings can accommodate a panel controller with operating and display unit as the central element The HCP 0006 A and HBC 0010 A basic housings can be extended to meet individual requirements using HBE 0012 A Modular Extension Housing for an additional 12 modules and 2 x 12 V 28 Ah batteries PSS 0002 A or PSB 0004 A Power Supply housings...

Page 21: ...ply units Batteries HCP 0006 A 1 1 2 x 28 Ah HBC 0010 A 1 1 2 x 28 Ah HBE 0012 A 1 2 x 28 Ah PSS 0002 A 1 2 x 28 Ah PSB 0004 A 1 4 x 28 Ah DIB 0000 A Installation Types Various types of installation are possible Surface mounted Installation in 482 6 mm 19 racks For surface mounting the housing is mounted directly on the wall For installation in 482 6 mm 19 racks the FRK 0019 A installation kit is ...

Page 22: ...cription 1 LSN loop classic or improved version 2 Conventional stub with EOL resistor or EOL module optional conventional loop The tables below list the various product groups with all compatible peripheral devices The devices approved for connection to the CZM 0004 A Conventional Module or the FLM 420 4 CON Conventional Interface Module can be found in the relevant compatibility lists at www bosc...

Page 23: ...WI 270 Aspirating smoke detector FAS 420 TM FAS 420 TP TT LSN 0300 A LSN 1500 A FCS 320 TM FCS 320 TP CZM 0004 A FLM 420 4 CON Linear smoke detectors FIRERAY3000 FIRERAY5000 CZM 0004 A FLM 420 4 CON FRAY ONE EN FLM 420 RHV Linear heat detectors FCS LHD 2EN FLM 420 I8R1 Infrared flame detectors 016519 016589 CZM 0004 A FLM 420 4 CON Duct smoke detectors FAD 420 HS EN LSN 0300 A LSN 1500 A Product g...

Page 24: ...300 A LSN 1500 A FNM 420 FNM 420U FNM 420V LSN 0300 A LSN 1500 A PA 5 PA 10 SSM FLM 420 NAC NZM 0002 A Visual notification appliances FNS 320 SOL LX PY X M 10 SSM FLM 420 NAC NZM 0002 A FNS P400RTH RMH 0002 A FNS 420 R LSN 0300 A LSN 1500 A Product group Product name Interface Interface modules ATB 420 ATG 420 BAT 100 FLM 420 4 CON FLM 420 NAC FLM I 420 S FLM 420 RHV FLM 420 RLV1 FLM 420 RLV8 S FL...

Page 25: ... name Interface Key deposits FMS KR BASIC FMS KR BASIC RPF ENO 0000 B Product group Product name Interface Door controls Automatic fire detectors FAA MSR 420 FMD GT60 FMD GT50 FMD GT50 SPACE FLM 420 RHV TSZ 0400 FLM 420 I2 Product group Product name Interface Power supplies FPP 5000 FPP 5000 TI13 FPP 3000 ZSP135 FLM 420 I2 2 7 Networking i Notice You will find detailed information about the CAN an...

Page 26: ...ification appliances or administration of switch off by the building management system requires an individual EN54 certification of the overall system by a certification body 2 9 Connection to a voice alarm system The PRAESENSA Praesideo PAVIRO or Plena voice alarm system can be connected via a data transmission line to the panel This enables the panel to control voice alarm zones The control can ...

Page 27: ...AVENAR panel AVENAR panel series en 27 Bosch Sicherheitssysteme GmbH System manual 2022 07 5 0 F 01U 378 910 Plena RS232 LSN 3m Figure 2 7 Connecting a Plena Voice Alarm System ...

Page 28: ...nt and input which is able to set off an alarm requires a detection point Inputs are considered as detection points if they are programmed accordingly using the FSP 5000 RPS Programming Software In accordance with EN 54 2 no more than 512 detectors and their functions may fail if a system component fails 12 V 45 Ah batteries can only be used with the frame installation housings Use fuses complying...

Page 29: ...hich one of the following settings is programmed as the Message type are regarded as detection points Fire Internal fire Supervisory Multi criterion Smoke Fault Heat Water Only some of these message types are available for selection depending on the element type The elements and inputs that can trigger an alarm include all manual and automatic detectors as well as the modules and interface modules...

Page 30: ...classic mode with automatic addressing T tapping not possible maximum number of elements 127 Table 3 2 Address setting with rotary switches The rotary switches are moved to the required position using a slotted head screwdriver Automatic Address Setting If addresses are automatically allocated by a fire panel LSN improved all elements must have the address 0 0 0 factory default setting Manual Addr...

Page 31: ...ing not only loop or stub but also T tap topologies are possible As long as the maximum number of 254 elements is not exceeded the LSN improved network allows branches anywhere along the LSN line with any number of nodes any number of branches per node and any number of elements per branch Consider that mesh structures are not allowed It is essential to ensure that no mesh structures are created L...

Page 32: ...s setting LSN 0300 A LSN 1500 A LSN 0300 A LSN 1500 A Loop Stub Table 3 4 Topologies in LSN improved with automatic address setting Stub topology Each LSN element provides a built in isolator between the b1 and b2 connectors The current flows through the LSN element between b1 and b2 Therefore the last element of the stub has only incoming but no outgoing cable Unlike for the loop topology the dir...

Page 33: ...ments between the two isolating elements will be disconnected The number of non isolating elements between two isolating elements must thus be limited in number according to local regulations Additionally activate in FSP 5000 RPS under Network Settings the feature Detector Removal Feature in T Tap Previously removed detectors can be reinserted back into their bases After a reset of the LSN line th...

Page 34: ...ng systems in accordance with VdS 2496 If a signal processing unit fails no more than one extinguishing area may fail In such cases redundant system components must be used Redundant panel controller Redundant LSN 0300 A module when using more than one FLM 420 RLE S in an LSN loop For installation reasons only 42 modules can be programmed when configuring a redundant panel Without redundancy 46 mo...

Page 35: ...0 012 A Iflash flash current 0 018 A Note that the sum of non isolated cables must not exceed the limit of 500 m The limit of 500 m applies to The lines on the inputs of the following modules FLM 420 RHV FLM 420 I2 FLM 420 I8R1 S FLM 420 O8I2 S FLM 420 O1I1 FLM 420 RLE S The NAC line of the FLM 420 NAC module The lines to remote indicators FAA 420 RI DIN FAA 420 RI ROW The limit of 500 m non isola...

Page 36: ...ceed the limit of 1600 m 0 0 0 2 0 0 4 0 0 6 0 0 8 0 0 0 1 0 0 2 1 0 0 4 1 0 0 6 1 0 0 8 1 0 0 0 2 A m 7 0 A m 1 A m 5 1 A m 0 2 A m 0 1 A m 5 7 A m 5 A m 2 A m 4 A m 5 4 A m 5 2 A m 3 A m 5 3 3 1 0 2 1 0 1 1 0 0 1 0 9 0 8 0 7 0 6 0 5 0 4 0 3 0 2 0 1 0 0 A m 4 0 c a L m N b Figure 3 1 Diagram for determining the maximum achievable cable length LSN classic elements with LSN 0300 A L cable length in...

Page 37: ...d elements 254 d 300 mA limit 3 8 Achievable cable length with LSN 1500 A The usable cable length depends essentially on the resistance of the cable and the quantity and current consumption of the network elements The way in which the elements are distributed locally on the bus also makes a difference The possible cable length can be estimated using the formula below This formula is also used in t...

Page 38: ...nd open collector outputs Note that the maximum cable length must not exceed 3000 m Using the Diagram for LSN improved FET resistance 0 35 Ω fire alarm cable with Ø 0 8 mm Example 1 You want to know the maximum cable length for a given number of network elements and a given current consumption nE 120 INE 0 5 mA On the X axis go vertically up at 120 until you reach the 0 5 mA curve Then from the po...

Page 39: ... 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 N L m 0 7mA 1mA 1 5mA 20mA 10mA 7 5mA 5mA 2mA 4mA 4 5mA 2 5mA 3mA 3 5mA b 127 1 25mA 0 4mA 300mA a Figure 3 3 Diagram for determining the maximum achievable cable length LSN classic elements with LSN 1500 A L cable length in meters N number of LSN classic elements a 3000 m limit b maximum possible number of LSN classic elements 127 ...

Page 40: ...00 can be powered by up to 8 BCM 0000 B battery controller modules each with its own UPS 2416 A power supply unit Current consumption is equally distributed among all battery controller modules Notes The 24 V switch outputs may not be connected in parallel The total current for all connected components including the battery charge current may not exceed 6 A The batteries connected to the BCM must ...

Page 41: ... S 1 2 BCM 0000 B 24V 24V MAIN BAT1 BAT2 FAULT FAULT AC BAT MAIN POWER MAIN POWER TROUBLE TROUBLE TROUBLE BATTERY 1 BATTERY 2 S 1 2 A 6 1 4 2 S P U A 6 1 4 2 S P U A 2 0 0 0 S S P 12 V 28 Ah 12 V 28 Ah 12 V 28 Ah 12 V 28 Ah 12 V 28 Ah 12 V 28 Ah 12 V 28 Ah 12 V 28 Ah Figure 3 5 Configuration of 1 to 4 BCM modules wall mounting Configuration with 1 to 4 BCM 0000 B modules in frame installation hous...

Page 42: ...V 45 Ah 12 V 45 Ah 12 V 45 Ah 12 V 45 Ah 12 V 45 Ah 12 V 45 Ah 12 V 45 Ah Figure 3 6 Configuration of 1 to 4 BCM modules frame installation Configuration with 5 to 8 BCM 0000 B modules in wall mounting housings 2 BCM 0000 B modules on short panel rail 2 BCM 0000 B modules at the end of the long panel rail The remaining BCM 0000 B modules on a panel rail in the center of the system Each BCM 0000 B ...

Page 43: ... A 12 V 24 Ah 12 V 24 Ah 12 V 24 Ah 12 V 24 Ah A 6 1 4 2 S P U A 6 1 4 2 S P U A 2 0 0 0 S S P 12 V 28 Ah 12 V 28 Ah 12 V 28 Ah 12 V 28 Ah UPS 2416 A 12 V 24 Ah 12 V 24 Ah A 6 1 4 2 S P U 12 V 28 Ah 12 V 28 Ah UPS 2416 A UPS 2416 A UPS 2416 A Figure 3 7 Configuration with 5 to 8 BCM 0000 B modules wall mounting Limits The current load on a panel rail may not exceed the maximum value of 12 A The cu...

Page 44: ...battery capacity in Ah Possible capacities CBatt 24 26 Ah or 36 45 Ah with 2 batteries 48 52 Ah or 72 90 Ah with 4 batteries 3 10 Protective earth and equipotential bonding Country specific standards and guidelines must be considered e g DIN VDE 0100 540 particularly with regard to the protective function of the electrical safety These must be observed by qualified personnel 4 The UPS 2416 A power...

Page 45: ...trained specialist personnel Only use installation materials recommended by Bosch Otherwise interference resistance cannot be guaranteed Connection conditions set down by the regional authorities and institutions police fire service must be observed Environmental Conditions Assembly and operation of the fire panel must be carried out in a clean and dry indoor location Permissible relative humidity...

Page 46: ...found on the extranet This contains information about the wiring of the functional modules and the peripheral devices A printed short user guide in all relevant national languages with information on the most important functions on access level 1 and 2 is supplied with the panel controller A detailed user guide containing all relevant information on operating and configuring the panel can be found...

Page 47: ...anel controller Functional modules 4 After installation Store all documents 4 3 Installation of CPH 0006 A fully assembled panel The installation sequence is given by the numbers 1 to 9 UPS 2416 A PRD 0004 A PRS 0002 C CPH 0006 A 1 2 3 7 BCM 0000 B 12 V 45 Ah 5 12 V 45Ah 6 4 Module 8 4 FBH 0000 A FHS 0000 A HMP 0003 A Figure 4 1 Installation of CPH 0006 A fully configured panel ...

Page 48: ... 3 9 1 7 5 6 Figure 4 2 Installation of HCP 0006 A fully configured panel 4 5 Extended line monitoring VdS 2540 VdS 2543 Auxiliary power supplies to the following modules can be monitored for creeping short circuits and creeping open LSN 0300 A LSN 1500 A and BCM 0000 B when using FPP 5000 TI13 A creeping short circuit is detected by these modules An FPP 5000 TI13 forwards the faults detected and ...

Page 49: ...ies Figure 4 3 FPP 5000 External Power Supply Unit Kit 24 V 6 A Scope of Delivery PMF 0002 A Power Supply Housing Frame Installation medium FMH 0000 A Mounting Frame Medium Power supply bracket installed UPS 2416 A Universal Power Supply PRS 0002 C Panel Rail Short BCM 0000 B Battery Controller Module Requisite cable sets Can be Extended with 2 x 12 V 45 Ah batteries FPP 5000 TI Trouble Interface ...

Page 50: ...an be found in FPP 5000 TI Trouble Interface FPP 5000 TI13 Communication Interface The Communication Interface is an extension for the External Power Supply Unit Kit only It is the communication interface between the External Power Supply Unit Kit and the panel and transmits the following faults to the panel Mains fault Battery fault Battery internal resistance fault BCM Battery Controller Module ...

Page 51: ...nter time date PNA Physical Node Address Ethernet Settings and reboot the panel 4 Connect the panel controller to the PC via USB Make sure that the current version of the FSP 5000 RPS programming software is installed on your PC 5 Start the auto configuration Edit the configuration according to the requirements of the fire alarm system 6 Load the configuration to the panel controller 7 Start the w...

Page 52: ...conventional LSN loop Disconnect the conventional LSN loop by detaching the cable connection to the corresponding functional module Failure of the conventional LSN loop must be indicated on the display Restore the connection between the conventional LSN loop and the corresponding functional module and reset the error message Now test all automatic and manual detectors 2 Testing a conventional LSN ...

Page 53: ...s implies that when AVENAR panel and AVENAR keypad are running firmware V3 x they only contain bound product features and peripheral devices that are also available with MPC xxxx B and MPC xxxx C panel controllers Depending on the hardware platform firmware V3 x is available with two different file extensions CBIN MPC xxxx Band MPC xxxx C SWU AVENAR panel and AVENAR keypad Bosch recommends to upgr...

Page 54: ...Bosch logo to verify the software version 5 3 Storing trace files on a memory card AVENAR panel has the option to store trace files on a memory card for instance for an expert analysis when the system behaves unexpected To insert the memory card follow these steps 1 Get a FAT 32 formatted memory card 2 Disable the write protection of the memory card 3 Insert the memory card in a computer 4 If nece...

Page 55: ...AVENAR panel Commissioning en 55 Bosch Sicherheitssysteme GmbH System manual 2022 07 5 0 F 01U 378 910 i Notice Do not remove or rename files ...

Page 56: ...equired to be performed at least once a year Otherwise operating the device may be difficult or even not possible without prior re calibration For further information see the necessary procedure in the user guide Clean the touch screen and surfaces with a slightly damp soft cloth only Do not use any cleaning agents and make sure that no liquid enters the inside of the device Warranty Defective dev...

Page 57: ...panel can be upgraded with the latest AVENAR panel controller Consider the following checklist upfront Address cards AVENAR panel does not require address cards Make sure to order an AVENAR panel controller containing the right software license Check if the fire panel has an interface to Building management system via BIS OPC or FSI Hierarchy panel UGM 2040 Voice alarm system Smart Safety Link A p...

Page 58: ...g rail Do not use the second short rail anymore Refer to installation guide for FPE 8000 CRP Cable set redundant panel controller Firmware and configuration The panel controller which needs be replaced is perhaps still running on a firmware V1 x or V2 x When AVENAR panel needs be integrated in a panel network combined with FPA panel controllers type B and C it is mandatory to use the compatible fi...

Page 59: ...ted to the switch Removing the switch or moving the OPC or FSI interface to Ethernet port 3 will result in a changed autonomy When the configuration is not identical certainly when Ethernet port 3 or 4 are used it is mandatory to recalculate the battery capacity with the Safety Systems Designer Remote keypad When replacing a remote keypad it is mandatory to replace all the plastic parts as well Fo...

Page 60: ...ups with more than one FNM 420 per loop 6 Voice alarm system Max number In CAN network per panel premium license 1 In total Ethernet network premium license 1 Triggers each trigger counts as one sounder group Ethernet interface 244 Triggers each trigger counts as one sounder group RS 232 interface 120 Per fire panel Max number Sets e g bypass group These sets include sets which are automatically c...

Page 61: ...table objects including counters without pre defined system counters 2000 Automatic connections to remote keypad 3 Blocks of State Dependent Rules depending on what kind of activations are possible 8 Maximum number of rules within a block 254 Number of functional modules Max number ANI 0016 A 32 BCM 0000 B 8 CZM 0004 A 32 ENO 0000 B 8 FPE 5000 UGM 4 IOP 0008 A 32 IOS 0020 A 4 IOS 0232 A 4 LSN 0300...

Page 62: ...ach trigger counts as one sounder group Ethernet interface 244 Triggers each trigger counts as one sounder group RS 232 interface 120 Per fire panel Max number Sets e g bypass group These sets include sets which are automatically created for each LSN bus 192 Functional modules 6 Printer 4 Alarm counters external internal testing 3 Entries in the event database 10000 FSP 5000 RPS configuration inte...

Page 63: ...d of activations are possible 8 Maximum number of rules within a block 254 Number of functional modules Max number ANI 0016 A 4 BCM 0000 B 5 CZM 0004 A 4 ENO 0000 B 4 FPE 5000 UGM 4 IOP 0008 A 4 IOS 0020 A 4 IOS 0232 A 4 LSN 0300 A 4 LSN 1500 A 0 NZM 0002 A 4 RMH 0002 A 4 RML 0008 A 4 7 3 Maximum number of devices per functional module or interface module Module Device Max number Further informati...

Page 64: ...ithout detector FWI 270 10 Any manual call point 21 FLM 420 EOL2W W FLM 420 EOL4W 10 FWI 270 FDOOT271 O FDM273 O FDM275 O 30 NZM 0002 A SOL LX 11 1 Hz 18 0 5 Hz PA 5 2 PA 10 SSM 1 7 4 Power loss of panel components i Notice Power loss of components typical In the data sheet of the system you will find more detailed information on the listed typical power loss values Component Power loss ANI 0016 A...

Page 65: ...00 SPC max 10 W IOP 0008 A 0 24 W IOS 0020 A 0 36 W IOS 0232 A 0 36 W LSN 0300 A 1 50 W AUX with 490 mA load 2 72 W LSN LSN 1500 A 8 00 W AUX 14 70 W LSN with 750 mA load NZM 0002 A 0 96 W PRD 0004 A 0 07 W PRS 0002 C 0 07 W RMH 0002 A 1 16 W RML 0008 A 1 04 W all relays activated UPS 2416 A 28 00 W 7 5 FPP 5000 External Power Supply Unit Kit 24 V 6 A For further information refer to the FPP 5000 ...

Page 66: ...ts Complete failure of power supply Output to fault signaling transmission equipment Disabled status Disabling of addressable points Test status Daymode status 8 2 Controlling Extinguishing Systems The fire panel enables the activation of extinguishing systems with the extinguishing interface described in VDE 0833 Part 2 or by the VdS standard interface SST in line with VdS 2496 Connection occurs ...

Page 67: ...mounting frames and installation kits Panel housings for frame installation Designation Installation manual ID CPH 0006 A Modular Panel Housing for 6 Modules Frame Installation 4998154002 MPH 0010 A Modular Panel Housing for 10 Modules Frame Installation 4998154002 Extension housings for frame installation Designation Installation manual ID EPH 0012 A Modular Extension Housing for 12 Modules 49981...

Page 68: ...0 8 3 2 Wall mounting housings and installation kits Panel Housings for Wall Mounting Designation Installation manual ID HBC 0010 A Modular Panel Housing for 10 Modules 4998153994 HCP 0006 A Modular Panel Housing for 6 Modules 4998153994 Extension Housings for Wall Mounting Designation Installation manual ID DIB 0000 A Distribution Box F01U003105_610 HBE 0012 A Modular Extension Housing for 12 Mod...

Page 69: ...s Designation Installation manual ID FPP 5000 External Power Supply Unit Kit F01U005065 FPP 5000 TI Trouble Interface for FPP 5000 F01U081396 FPP 5000 TI13 LSN Communication interface for FPP 5000 F01U164562 UPS 2416 A Universal Power Supply 24 V 6 A F01U003349 FPO 5000 PSB CH Power Supply Bracket F01U079870 FPO 5000 PSB1 Power Supply Bracket F01U079868 8 3 6 Panel controller remote keypad Install...

Page 70: ...82 CZM 0004 A 4 Zone Conventional Module 4998153977 ENO 0000 B Fire Service Interface Module F01U063946 FPE 5000 UGM Interface Module F01U028306 IOP 0008 A Input Output Module 4998153976 IOS 0020 A 20 mA Communication Module 4998153974 IOS 0232 A RS232 Communication Module 4998153975 LSN 0300 A LSN improved Module 300 mA 4998153984 LSN 1500 A LSN improved Module 1500 mA 4998153983 NZM 0002 A Notif...

Page 71: ...irements 66 EOL 28 Ethernet interface 7 Extinguishing systems Activation 66 Extranet 26 46 57 F Fire detector cable 28 Fire service Devices 25 FLM 420 4 CON 28 FSP 5000 RPS Programming Software 8 51 Functional module 10 Functional test 51 H Height unit 68 Housing frame installation 17 Installation types 21 Scope of delivery 19 Versions 7 Wall mounting 20 I Installation 45 Documentation 46 57 Instr...

Page 72: ...26 60 62 R Redundancy 28 29 34 Keypad 34 Panel controller 34 Remote keypad 17 34 S Safety Instructions 5 Safety Systems Designer 9 10 28 System limits 35 38 60 61 62 T Technical data Power loss 65 000 000 000 000 000 000 System limits 60 61 62 Test Addressing activation 52 Conventional LSN functions 52 Power supply 52 Thermal printer 9 Touch screen 14 Trouble Interface 49 U Universal security syst...

Page 73: ...AVENAR panel Index 73 Bosch Sicherheitssysteme GmbH System manual 2022 07 5 0 F 01U 378 910 ...

Page 74: ...74 Index AVENAR panel 2022 07 5 0 F 01U 378 910 System manual Bosch Sicherheitssysteme GmbH ...

Page 75: ......

Page 76: ...Bosch Sicherheitssysteme GmbH Robert Bosch Ring 5 85630 Grasbrunn Germany www boschsecurity com Bosch Sicherheitssysteme GmbH 2022 202207221041 Building solutions for a better life ...

Reviews: