20
en | AVENAR panel series
AVENAR panel
2022-07 | 5.0 | F.01U.378.910
System manual
Bosch Sicherheitssysteme GmbH
2.5
Housings for wall mounting
Figure 2.4:
Housings for wall mounting
Wall mounting housings are screwed directly onto the wall. This reduces the installation depth
by approx. 9 cm, although the smaller 12 V/28 Ah batteries must be used as a result.
The modular system makes it easy to extend the system.
Housing Designs and Combinations
Two wall mounting housings are available as a base unit:
–
HCP 0006 A (for 6 modules), and
–
HBC 0010 A (for 10 modules)
These housings can accommodate a panel controller with operating and display unit as the
central element.
The HCP 0006 A and HBC 0010 A basic housings can be extended to meet individual
requirements using:
–
HBE 0012 A Modular Extension Housing for an additional 12 modules, and 2 x 12 V/28 Ah
batteries
–
PSS 0002 A or PSB 0004 A Power Supply housings for additional power supply units and
12 V/28 Ah batteries
Equipment Limits
The table below shows the maximum number of:
–
Modules
–
Panel rails (short PRS-0002-C, long PRD 0004 A)
Housing type
Modules
Short rail
Long rail
HCP 0006 A
6
1
1
HBC 0010 A
10
1
2
HBE 0012 A
12
-
3
PSS 0002 A
-
-
-
PSB 0004 A
-
-
-
DIB 0000 A
-
-
-