background image

ARD‑FPBEW2‑H3 Fingerprint Reader, Multiclass

ARD‑FPBEW2‑H3

en

Installation manual

Summary of Contents for ARD-FPBEW2-H3

Page 1: ...ARD FPBEW2 H3 Fingerprint Reader Multiclass ARD FPBEW2 H3 en Installation manual ...

Page 2: ......

Page 3: ...les and connectors 8 2 4 How to enroll a fingerprint 10 3 Installation 12 3 1 Fixing the bracket and the product 12 3 2 Power supply connection 14 3 3 Network connection TCP IP 15 3 4 Wiegand connection 16 3 5 RS485 connection 17 3 6 Resetting network settings 17 3 7 Restoring the factory defaults 17 4 Technical data 18 4 1 Product specifications 18 4 2 Dimensions 20 5 UL 21 5 1 UL 294 requirement...

Page 4: ...When installing more than one device allow space between the devices i Notice In case of malfunction contact Bosch After Sales Service Do not attempt to repair the product yourself or free after sales service will not be provided Old electrical and electronic equipment This product and or battery must be disposed of separately from household waste Dispose such equipment according to local laws and...

Page 5: ...urity reasons the use of the Wiegand interface is not recommended A secure encrypted data connection is only obtained with the use of the OSDP v2 protocol The OSDP protocol is used via the RS485 connection i Notice To ensure high security of data exchange between credentials and readers only encoded cards such as MIFARE DESFire or iCLASS SE should be used in the access system ...

Page 6: ... v01 Installation manual Bosch Access Systems GmbH 2 Introduction 2 1 Components ARD FPBEW2 Bracket Ferrite Core 1 EA Bracket Fixing Screw Star Shaped PVC anchor 2 EA Heat shrink Fixing screw 2 EA Drilling template OSS Manual Safety Instructions Quick Installation Guide ...

Page 7: ...erational status of the product with the color of the LED lamp 2 RF card authentication unit Reads RF cards for entering and exiting 3 Fingerprint authentication unit Reads fingerprints placed on it for entering and exiting 4 Reset button For details see chapters 3 6 and 3 7 5 LED lamp for Network Shows the status of the network connection 6 Cable Wiegand cable Power cable RS485 cable Ethernet con...

Page 8: ...ngerprint Reader Multiclass 2022 06 v01 Installation manual Bosch Access Systems GmbH 2 3 Cables and connectors Cut the required wires off the connector plug Cable Cable name A Wiegand cable B Ethernet cable C Power cable D RS485 cable ...

Page 9: ...tripe 3 WG Tamper NC Orange White stripe 4 Not used Blue Brown 5 Not used Red Green 6 WG D0 Green 7 WG D1 White 8 WG GND Black 9 WG LED red Brown 10 WG LED green Purple 11 PWR VDC Red 12 Not used Pink 13 PWR GND Black White stripe 14 485 TRXN RxTx Yellow Black stripe 15 485 TRXP RxTx Blue White stripe 16 485 PAG White Black stripe 17 ENET TXP White 18 ENET TXN Orange 19 ENET RXP Black 20 ENET RXN ...

Page 10: ...gets hurt up to 10 fingerprints for each user can be registered In the case of a user whose fingerprint cannot be recognized well the authentication rate can be improved by enrolling the same finger twice repeatedly If a finger has a cut or the fingerprint is blurry select another finger for the fingerprint It is recommended to use the index finger or the middle finger when scanning the fingerprin...

Page 11: ...he finger upright so that the contact area with the sensor has decreased or the angle of finger has warped fingerprint authentication may not be performed Failure during fingerprint recognition The reader can recognize a fingerprint regardless of a change of season or finger condition However the authentication rate may vary according to the external environment or fingerprint input method If the ...

Page 12: ...et using the provided drilling template 2 Fix the bracket firmly using fixing screws through the bracket to the position where the device will be installed 3 Install the device onto the fixed bracket 4 Assemble the device to the bracket by rotating the star shaped fixing screw When assembling the product with the bracket use the included bracket fixing screw star shaped instead of the product fixi...

Page 13: ...nual 2022 06 v01 Installing the device on a concrete wall 1 Drill holes on the wall 2 Insert the PVC anchors 3 Fix the anchors with fixing screws 4 Maintain a minimum separation distance to avoid RF interference see table below 30 cm 30 cm Wall thickness Distance 100 mm 270 mm 120 mm 250 mm 150 mm 170 mm ...

Page 14: ...UPS Optional 12V DC 11 PWR VDC 13 PWR GND Red Black White stripe Warning When connecting to an AMC2 4R4CF controller note that the 12V power supply is used Warning Do not connect the device to the DC power supply or adapter and PoE power supply at the same time i Notice Make sure to isolate the power connector cables if PoE is used for power supply ...

Page 15: ...nnection TCP IP LAN connection connecting to a hub You can connect the product to a hub using a general type CAT 5 cable or higher LAN connection connecting to a PC directly The ARD FPBEW2 has an automatic MDI MDIX function so that it can be connected to a PC directly using a normal straight type CAT 5 cable or higher not a cross cable ...

Page 16: ...ion 1 2 3 6 7 8 9 10 WG Tamper NO WG Tamper COM WG Tamper NC WG D0 WG D1 WG GND WG LED Red WG LED Green Gray White stripe Green White stripe Orange White stripe Green White Black Brown Purple Control device 1 2 3 6 7 8 9 10 i Notice When using the Wiegand interface there is only an optical LED and no acoustic feedback buzzer from the reader ...

Page 17: ...default values TCP IP address DHCP address assignment If DHCP address assignment is fails 169 254 x x will be set Server mode Disabled RS 485 PC connection 115200 bps 4 Change the TCP IP address or RS 485 information 5 Turn the power off later on and then check the network setting is properly 3 7 Restoring the factory defaults This will delete all data and root certificate on the device and reset ...

Page 18: ...5 Host interface Ethernet Electrical Operating voltage VDC 12 VDC Current consumption mA 600 mA Environmental IP rating IP67 Impact protection EN 50102 IK09 Operating temperature C 20 C 50 C Operating temperature F 4 F 122 F Operating relative humidity non condensing 0 80 Storage relative humidity 0 90 Storage temperature C 40 C 70 C Storage temperature F 40 F 158 F Mechanical Material Polycarbona...

Page 19: ...2 HID Prox Seos HID Corporate 1000 MIFARE DESFire EV2 Protection Tamper micro switch Storage Storage templates Template on device Template in secure database of AMS or BIS ACE System requirements Memory RAM MB 256 MB Processor type 1 2 GHz Quad Core For more information on templates refer to BIS ACE and AMS installation manuals i Notice Data stored in the reader can be deleted by the Operator thro...

Page 20: ...20 en Technical data ARD FPBEW2 H3 Fingerprint Reader Multiclass 2022 06 v01 Installation manual Bosch Access Systems GmbH 4 2 Dimensions ...

Page 21: ...2022 06 v01 5 UL 5 1 UL 294 requirements The following UL 294 levels apply Destructive attack level 2 Line security level 2 Endurance level 1 Standby power level 1 If the unit is powered by an external power supply you can use UL Listed Class 2 power supply with 12VDC UL 294B Listed PoE power source ...

Page 22: ...es and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on th...

Page 23: ......

Page 24: ...Bosch Security Systems B V Torenallee 49 5617 BA Eindhoven Netherlands www boschsecurity com Bosch Security Systems B V 2022 202206301752 Building solutions for a better life ...