Grounding and Shielding
The main grounding point at the AMC2-4R4 is connected to pin
2 of the power supply connector – see Connecting Diagrams,
page 58.
It is good practice to shield all wires carrying low level signals.
The AMC2-4R4 allows you to create a central ground or
shielding point, simply by setting certain jumpers. Set these
jumpers only if grounding or shielding is not achieved by other
means.
Notice!
Risk of malfunction
Ensure that no ground loops are formed.
Notice!
In general the following apply:
If the devices have their own power supplies, the shielding is
applied to one side only. The free end should be insulated to
avoid inadvertent connections.
If one device is fed power by another, the cable shielding
should be applied to both sides.
4.6
Access Modular
Controller
Installing | en
25
Bosch Sicherheitssysteme GmbH
2013-08 | AMC2-4R4 |