UPSaver
installation and start-up
84
OMH44149 REV. C
5.5
RESTART FROM MANUAL BYPASS
Before restarting the UPS from manual by-pass, make sure the
Bypass_Sw
selector is in
BYPASS
position and the MBCB isolator is closed.
1)
Close the general switch RCB inside the I/O module. After some seconds the
touch
screen
will start, which will shown the start-up screen with the
UPSaver
logo.
2)
After the software loading phase the control logic will acquire the system status and the
operation of the RCB switch, and will give the first operating instruction as shown in the
picture below. Choose the
NORMAL STARTUP
option and then close the general
switch SBCB as requested.
Picture 91 – I/O module start-up
Picture 92 – I/O module start-up