UPSaver
installation and start-up
68
OMH44149 REV. C
4.3.1 Connection bars position
The tables that follow indicates the distance of the connection bars from a defined reference
point:
For
bottom
cables entry the distance is given
from the ground
(cabinet base)
For
top
cables entry the distance is given
from the roof
(cables entry plate)
The distance is referred to the first available hole.
Bottom cables entry
Distance from ground [mm]
Connection
Bar
I/O 800kVA
I/O 1200kVA
I/O 1600kVA
Rectifier
L1 1060
415
Contact the manufacturer
L2 900
415
L3 770
415
Bypass
L1 680
1235
L2 520
1235
L3 380
1235
UPS output
L1 1060
715
L2 900
715
L3 770
715
Battery
+B
415 500
N
-B
Rect. / Byp. / Out. Neutral
N
1200
430
PE Earth
375
430