UPSaver
installation and start-up
58
OMH44149 REV. C
Details of the electrical connections
Potenza
(kVA)
400 600 800 1000 1200 1400 1600
Input fuses [A]
Rectifier
800 1250 1600
2x
1000
2x
1250
2x
1250
2x
1600
Bypass
1000 1600
2x
1000
2x
1250
2x
1600
2x
1600
2x
2000
Phase conductor cross sect. [mm
2
]
Rectifier
2x150 2x300 3x240 4x240 4x240 Barra
3200A
Bypass
2x150 2x240 3x240 3x240 4x240 5x240 6x240
Output
2x150 2x240 3x240 3x240 4x240 Barra
3200A
Battery
(1)
CB
(2)
2x150 2x300 3x240 4x240 4x300
-
-
DB
(3)
1x150
(x 2)
1x150
(x 3)
1x150
(x 4)
1x150
(x 5)
1x150
(x 6)
1x150
(x 7)
1x150
(x 8)
Neutral conductor cross section
Linear load
Same as the phase conductor
NON-linear load
1,5
x phase conductor cross section
Earth conductor cross sect. [mm
2
]
1x185 2x150 2x185 2x240 2x300 2x300 3x240
Power connections
Type
Copper / aluminium bars
Conductor max. cross section [mm
2
]
300
Max. number of conductors
4
Fixing bolt dimension
M16
Tightening torque [Nm]
170 +/- 20%
(1)
For the battery connection 3 groups of cables are needed, one for each polarity plus the central point (N)
(2)
Suggested cables for centralized battery configuration (
single battery
)
(3)
Suggested cables for distributed battery configuration (
one battery for each power module
)
The data detailed in the table above are indicative only. In designing the cables the rated
current carrying capacities given by the CEI-UNEL35024/1 table have been taken into account,
related to copper cables with PVC insulation sheath, with a maximum temperature of 70° C,
without applying any de-rating factor
.
The given cross sections do not take into account the
overload currents allowed by each line, which are detailed in the product Technical
Specification. In case of different installation methods or operating temperatures higher than 70°
C, apply the corrective factor according to the standards in force in the country of installation.
Rated current (at full load and battery recharging)
Power
(kVA)
400 600 800 1000
1200
1400
1600
Rectifier input [A]
(1)
677 1015 1353 1690 2029 2367 2705
Bypass input / Output [A]
(1) (2)
577 866 1155 1443 1732 2021 2309
Battery [A]
(3)
347
(1)
Values referred to 400Vac rated voltage
(2)
For the overload values please refer to the Technical Specification
(3)
Current drawn by each power module at the minimum discharge voltage
Summary of Contents for UPSaver 1000 kVa
Page 2: ...UPS OPERATING MANUAL UPSaver 400 1600 kVA ...
Page 5: ......
Page 7: ...Warnings and general information 2 OMH44148 REV A ...
Page 13: ......
Page 20: ...UPSaver installation and start up OMH44149 REV C 7 ...
Page 33: ...UPSaver installation and start up 20 OMH44149 REV C Picture 6 Handling of the power module ...
Page 57: ...UPSaver installation and start up 44 OMH44149 REV C Picture 46 UPS cabinets upper fixing ...
Page 59: ...UPSaver installation and start up 46 OMH44149 REV C Picture 49 Power module cables terminals ...
Page 115: ...UPS user manual 6 OMH44150 REV B ...