UPSaver
installation and start-up
38
OMH44149 REV. C
Classification of chemically active substances (EN 60721-3-3)
Environmental parameter
Class
3C1R
3C1L
3C1
3C2
3C3
3C4
a)
Sea salt
No
No
No
Salt
fog
Salt
fog
Salt
fog
b)
Sulphur dioxide
[mg/m
3
]
0,01 0,1 0,1 1,0 10 40
c)
Hydrogen sulphide
[mg/m
3
]
0,0015 0,01 0,01 0,5
10
70
d)
Chlorine [mg/m
3
]
0,001 0,01 0,1 0,3 1,0 3,0
e)
H
ydrochloric acid
[mg/m
3
]
0,001 0,01 0,1 0,5 5,0 5,0
f)
H
ydrofluoric acid
[mg/m
3
]
0,001 0,003 0,003 0,03 2,0 2,0
g)
Ammonia [mg/m
3
]
0,03 0,3 0,3 3,0 35 175
h)
Ozone [mg/m
3
]
0,004 0,01 0,01 0,1 0,3 2,0
i)
Nitric oxide (expressed in equivalent values of
nitrogen dioxide) [mg/m
3
]
0,01 0,1 0,1 1,0 9,0 20
Places where atmosphere is strictly monitored and
regulated (“clean spaces” category)
X
Places where atmosphere is permanently
monitored
X
Places located in rural and urban
regions where
industrial activities are few and where traffic
is moderate
X
Places located in urban regions with industrial
activities and/or considerable traffic
X
Places in proximity to industrial sources with
chemical emissions
X
Places located in industrial installations.
Emissions of highly concentrated chemical
pollutants
X
The
UPSaver
UPS is designed to be installed in an environment that meets the following
classifications.
K Climatic
conditions
In accordance with the technical
specification
B Biological
conditions
3B1 (EN 60721-3-3)
C
Chemically active substances
3C2 (EN 60721-3-3)
S
Mechanically active substances
3S2 (EN 60721-3-3)
In the event that the environmental conditions of the installation room do not comply with the
specified requirements, additional precautions must be taken to reduce excessive values to the
specified limits.
Summary of Contents for UPSaver 1000 kVa
Page 2: ...UPS OPERATING MANUAL UPSaver 400 1600 kVA ...
Page 5: ......
Page 7: ...Warnings and general information 2 OMH44148 REV A ...
Page 13: ......
Page 20: ...UPSaver installation and start up OMH44149 REV C 7 ...
Page 33: ...UPSaver installation and start up 20 OMH44149 REV C Picture 6 Handling of the power module ...
Page 57: ...UPSaver installation and start up 44 OMH44149 REV C Picture 46 UPS cabinets upper fixing ...
Page 59: ...UPSaver installation and start up 46 OMH44149 REV C Picture 49 Power module cables terminals ...
Page 115: ...UPS user manual 6 OMH44150 REV B ...