3.3.5 Environmental installation conditions
The air is classified by the EN 60721-3-3 standard (Classification of environmental
parameters and their severities – Stationary use at weather-protected locations) based on
climatic and biological conditions as well as on mechanically and chemically active substances.
Therefore the place of installation must meet specific requirements to ensure compliance
with the conditions for which the UPS was designed.
Climatic conditions according to the
UPSaver
technical specification
Environmental parameter
Minimum operating temperature (°C)
– 10
Maximum operating temperature (°C)
+ 40
Minimum relative humidity (%)
5
Maximum relative humidity (%)
95
Condensation
NO
Rainfall with wind (rain, snow, hail, etc.)
NO
Water with an origin other than rain
NO
Ice formation
NO
Classification of biological conditions (EN 60721-3-3)
Environmental
parameter
Class
3B1
3B2
3B3
a)
Flora
NO
Presence of mildew, fungus,
etc.
Presence of mildew, fungus,
etc.
b)
Fauna
NO
Presence of rodents and
other animals that are
harmful to products,
excluding termites
Presence of rodents and
other animals that are
harmful to products,
including termites
Classification of mechanically active substances (EN 60721-3-3)
Environmental parameter
Class
3S1
3S2
3S3
3S4
a)
Sand [mg/m
3
]
No
30 300
3000
b)
Dust (suspension) [mg/m
3
]
0,01 0,2 0,4 4,0
c)
Dust (sedimentation) [mg/(m
2
·h)
0,4 1,5 15 40
Places where precautions have been taken to minimize the presence
of dust. Places away from dust sources
X
Places without any special precaution to minimize the presence of
sand or dust, however not in proximity to sand or dust sources
X
Places in proximity to sand or dust sources
X
Places in proximity to working processes that generate sand or dust,
or in geographic areas having a high proportion of sand brought by
the wind or of dust suspended in the air
X
Summary of Contents for UPSaver 1000 kVa
Page 2: ...UPS OPERATING MANUAL UPSaver 400 1600 kVA ...
Page 5: ......
Page 7: ...Warnings and general information 2 OMH44148 REV A ...
Page 13: ......
Page 20: ...UPSaver installation and start up OMH44149 REV C 7 ...
Page 33: ...UPSaver installation and start up 20 OMH44149 REV C Picture 6 Handling of the power module ...
Page 57: ...UPSaver installation and start up 44 OMH44149 REV C Picture 46 UPS cabinets upper fixing ...
Page 59: ...UPSaver installation and start up 46 OMH44149 REV C Picture 49 Power module cables terminals ...
Page 115: ...UPS user manual 6 OMH44150 REV B ...