UPSaver
installation and start-up
OMH44149 REV. C
25
The supporting base of the UPS must be designed to carry the UPS weight and to ensure its
steady and safe support.
Its carrying capacity must be adequate to the static loads indicated in the table below.
Weight
[kg]
Static load
[kg/m
2
]
Config. UPSaver
CB+CSB CB+DSB
DB+CSB
DB+DSB
CB+CSB CB+DSB
DB+CSB
DB+DSB
Power module
570
1030
400
kVA
I/O
module 660 650 650 520 620 610 610 490
600
kVA
I/O
module 690 680 680 550 650 640 640 520
800
kVA
I/O
module 780 770 770 640 560 560 560 460
1000 kVA I/O module
1140
890
990
740
670
520
720
540
1200 kVA I/O module
1170
920
1020
770 690 540 740 560
1400 kVA I/O module
Contact the manufacturer
1450
Contact the manufacturer
560
1600 kVA I/O module
Contact the manufacturer
1490
Contact the manufacturer
575
3.3.3 System layout and overall dimensions
Picture 13 – UPSaver power module