UPS user manual
18
OMH44150 REV. B
3.3.4 UHE mode – Ultra High Efficiency
Picture 16 – UHE mode
The UHE mode is the one that guarantees the higher efficiency, since during the normal
operation all the system power converters (rectifier and inverter) are off and the loads are
directly supplied by the mains via the static switch. In such configuration a section of the rectifier
is permanently on in order to supply the control logic and safeguard the battery which would
otherwise supply energy, although in a very limited quantity. Therefore the battery static switch
is kept open and is operated only in case of mains failure.
Should the mains fail the inverter is started and the load is transferred through the static
switch. The disturbance on the output voltage is fully within both the limits defined by the ITIC
(information Technology Industry Council) and the curve 3 of the dynamic performance defined
by the EN 62040-3 standard.
Picture 17 – UHE mode, mains failure