redundancy algorithm, which has been explained previously, therefore is is activated only if the
output load is such to allow to have at least one power module off to be used as "reserve".
3.3.2 VHE mode – Very High Efficiency (Line Interactive)
In the VHE mode the load is supplied by the mains via the static bypass switch; the inverter
operates as a active filter to stabilize the output voltage should the mains parameters be beyond
the availability and stability pre-defined limits, which are controlled by a dedicated algorithm (VI
– Voltage Independent). Such function can be enabled and is automatically managed by the
above mentioned algorithm on the basis of both the load and AC supply conditions.
In case of mains outage or anomaly occurring on the bypass line the load is transferred to
the inverter.
Picture 14 – VHE mode
3.3.3 ECO
mode
Similarly to the VHE mode, the load is supplied by the mains in the ECO mode as well; it
differs from the VHE mode because the inverter is on, in stand-by. Therefore it doesn't make
any "conditioning" on the output voltage, which is therefore dependent on the variation of the AC
input parameters (VFD – Voltage Frequency Dependent).
In case of mains outage or anomaly occurring on the bypass line the load is transferred to
the inverter; the transfer occurs with a short interruption of maximum 10 ms.
Picture 15 – ECO mode
Summary of Contents for UPSaver 1000 kVa
Page 2: ...UPS OPERATING MANUAL UPSaver 400 1600 kVA ...
Page 5: ......
Page 7: ...Warnings and general information 2 OMH44148 REV A ...
Page 13: ......
Page 20: ...UPSaver installation and start up OMH44149 REV C 7 ...
Page 33: ...UPSaver installation and start up 20 OMH44149 REV C Picture 6 Handling of the power module ...
Page 57: ...UPSaver installation and start up 44 OMH44149 REV C Picture 46 UPS cabinets upper fixing ...
Page 59: ...UPSaver installation and start up 46 OMH44149 REV C Picture 49 Power module cables terminals ...
Page 115: ...UPS user manual 6 OMH44150 REV B ...