Borri GIOTTO 1000VA User Manual Download Page 11

          

Modello  

bORRI GIOTTO UPS   bORRI GIOTTO UPS   bORRI GIOTTO UPS   bORRI GIOTTO UPS   bORRI GIOTTO UPS   bORRI GIOTTO UPS 

Capacità  

450VA/270W 

650VA/380W 

 850VA/500W 

 1000VA/600W 

 1500VA/900W 

 2000VA/1200W 

Ingresso 

        

Tensione 

220/230/240VAC 

Range tensione  

160~290Vac 

Uscita         

Regolazione di  

+/- 10%

tensione  

Forma d’onda  

Forma d’onda sinusoidale simulata 

batteria 

        

Tipo e numero 

12V/5Ah 

 x 1 12V/7Ah x 1 

 12V/9Ah x 1 

 12V/7Ah x 2 

 12V/7Ah x 2 

 12V/9Ah x 2 

Forma d’onda 

4-6 ore per il 90% della capacità 

Dati 

meccanici 

        

Dimensioni  

292 x 100 x 140 

 315 x 148 x 198

(PxLxA, mm)   

 

 

Peso(kg)  

 5  

5.5 

 9 

 10.5  

11.8 

Dimensioni   

 

imballaggio  

321 x 137 x 226 

 411 x 229 x 302

(PxLxA, mm)    

 

Dati 

ambientali 

        

Umidità 

0-90 % RH @ 0-40 C (senza condensa) 

Rumorosità 

< 40 dB 

Sicurezza 

        

Marcatura  

CE 

Sicurezza  

EN62040-1 

EMC  

EN62040-2 

Qualità  

ISO9001:2008, ISO 14001:2004, BSOHSAS 18001:2007 

bORRI GIOTTO UPS scheda tecnica

Se il gruppo di continuità non risulta funzionare correttamente 

si consiglia di eseguire i seguenti test prima di contattare 

l’assistenza.

Passi da controllare:

Passo 1:  l’interruttore principale è in posizione “ON”?

Passo 2:  l’UPS è collegato alla rete elettrica?

Passo 3:  I valori di alimentazione rientrano tra i valori indicate in  

 

specifica?

Passo 4:  Il fusibile è correttamente inserito nella presa?

Passo 5:  l’UPS è in sovraccarico?

Passo 6:  La batteria è scarica o difettosa?

 

  

  

Situazione  

  Cosa controllare  

  Soluzione 

Nessuna visualizzazione sul    Batteria scarica.  

  Ricaricare l’UPS per almeno 6 ore 

display del pannello frontale    Batteria non idonea. 

  Sostituire la batteria con la stessa tipologia presente. 

 

  L’UPS non è acceso. 

  Premere nuovamente l’interruttore per accendere l’UPS. 

L’allarme suona  

  L’UPS è in sovraccarico. 

  Rimuovere alcuni carichi. Prima di riconnettere l’UPS verificare    

continuamente quando la 

   

    che la capacità di carico corrisponda a quanto riportato in 

rete è normale. 

   

  specifica. 

Quando si presenta una 

  L’UPS è in sovraccarico. 

  Rimuovere alcuni carichi. 

mancanza rete i tempi di 

  La tensione della batteria è 

  Ricaricare l’UPS per almeno 8 ore

backup diminuiscono. 

  troppo bassa 

   

 

  Difetti della batteria causati dalla    Sostituire la batteria con la stessa tipologia presente.

 

  alta temperatura ambiente o dal 

 

  funzionamento improprio della

 

  batteria. 

   

La rete è normale ma il 

  Il cavo di alimentazione 

  Ricollegare correttamente il cavo di almentazione

display lampeggia. 

  è allentato 

   

 

RISOLUZIONE DEI PRObLEMI

Per le condizioni di garanzia vedere il sito al seguente indirizzo: www.borri.it/supporto

 

Per usufruire della garanzia verrà chiesto di compilare alcuni dati riportati nell’etichetta del prodotto 

presente sulla scatola e sul prodotto stesso.

Rev. A 15.01.15

OML59002

Pagina 9

Manuale operativo

450VA/650VA/850VA/1000VA/1500VA/2000VA

Summary of Contents for GIOTTO 1000VA

Page 1: ...450 VA 2000 VA User manual Line interactive UPS for home home and small office Manuale operativo Line interactive UPS per la casa home office e l ufficio www borri it ...

Page 2: ......

Page 3: ...curezza 6 Set up 3 Installazione 7 Front panel explanations 4 Descrizione pannello frontale 8 Rear panel explanations 4 Descrizione pannello posteriore 8 Replace battery 4 Sostituzione della batteria 8 Troubleshooting 5 Risoluzione dei problemi 9 Technical data 5 Scheda tecnica 9 User manual Manuale operativo Rev A 15 01 15 OML59002 ...

Page 4: ...peration Locate a protected place for installation Do not place anything on top of the equipment Do not pour liquids in the outer surfaces of the equipment and in the slots in the casing Always disconnect the equipment and check the absence of dangerous potentials before carrying out any maintenance If the equipment contains energy storage devices the input and output ports could remain energised ...

Page 5: ...ff and there is no power utility it s still possible to cold start the UPS unit to power the loads 5 Connect computer interface port Connect the optional interface cable to the USB interface port on the back of the UPS Connect to the computer See software document for installation instruction 6 Turn ON OFF the UPS Turn on the UPS Press the UPS On OFF Switch for approx 3 seconds then the Buzzer sou...

Page 6: ...the loads are not protected from power outages 1 Use a cross type screwdriver to remove the four screws from bottom shell 2 Take up top cover and battery cover 3 Loosen the black wire from the negative terminal and red wire from the positive terminal 4 Connect the battery leads to the new battery 5 Note Small sparks at the battery connectors are normal during connection 6 Slide the battery into th...

Page 7: ... fuse gone in the mains plug Step 5 Is the UPS overload Step 6 Is the battery flat or defective Situation Check Items Solution No LED display on the Low battery Charge the UPS at least 6 hours front panel Battery fault Replace the battery with the same type of battery The UPS is not turned on Press the power switch again to turn on the UPS Alarm continuously sounds The UPS is overload Remove some ...

Page 8: ...ficare un luogo protetto per l installazione Non appoggiare alcun oggetto sopra l apparecchiatura Non versare liquidi nelle superfici esterne dell apparecchiatura e nelle fessure dell involucro Disconnettere sempre l apparecchiatura e verificare l assenza di potenziali pericolosi prima di effettuare operazioni di manutenzione Se l apparecchiatura contiene dispositivi di accumulo energia le porte d...

Page 9: ...oftware In caso di blackout o disturbi della rete elettrica il software Borri Power Guardian provvede anche in assenza dell utente a chiudere i programmi aperti il sistema operativo e avvisare l utente via sms o via email Inoltre mostra diversi parametri dell UPS inclusa l autonomia della batteria Si prega di seguire i seguenti passaggi per scaricare ed installare il software gratuito 1 Vai al sit...

Page 10: ...lle interruzioni di corrente 1 Utilizzare un cacciavite a croce per rimuovere le quattro viti dal guscio inferiore 2 Rimuovere il coperchio superiore e il coperchio della batteria 3 Allentare il filo nero del terminale negativo e il filo rosso del terminale positivo 4 Connettere I cavi della batteria alla nuova batteria 5 Nota Piccole scintille sui connettori della batteria sono normali durante la...

Page 11: ...a presa Passo 5 l UPS è in sovraccarico Passo 6 La batteria è scarica o difettosa Situazione Cosa controllare Soluzione Nessuna visualizzazione sul Batteria scarica Ricaricare l UPS per almeno 6 ore display del pannello frontale Batteria non idonea Sostituire la batteria con la stessa tipologia presente L UPS non è acceso Premere nuovamente l interruttore per accendere l UPS L allarme suona L UPS ...

Page 12: ...Borri S p A Via 8 Marzo 2 52010 Bibbiena Arezzo Italy phone 39 0575 5351 fax 39 0575 561811 www borri it ...

Reviews: