![bonitron M3534B Customer Reference Manual Download Page 22](http://html.mh-extra.com/html/bonitron/m3534b/m3534b_customer-reference-manual_2787127022.webp)
M3534R 20A
22
Table 4-5: Control Status Signal Component Specifications
B
OARD
T
ERMINAL
T
YPE
F
UNCTION
E
LECTRICAL
S
PECIFICATIONS
M
IN
W
IRE
AWG
M
AX
W
IRE
AWG
T
ORQUE
LB
-
IN
3534R2
Phoenix plug
TB5
Status
120VAC / .5 Amp
1kV Isolation
22
16
2 lb-in
Phoenix plug
TB3
Test
24VDC / 20mA
3kV Isolation
22
16
2 lb-in
Phoenix plug
TB4
Disable
24VDC / 20mA
3kV Isolation
22
16
2 lb-in
Table 4-6: Fault / Status Contact Logic Details
– 3534R2 Board
RTM
F
AULT
/
S
TATUS
C
ONDITION
I
NDICATORS
J
UMPER
P
OSITIONS
&
C
ONTACT
S
TATES
PWR
OT
RTA
OT
(J1)
RTA
(J2)
(LD1) (LD2) (LD3) N.C.
N.O.
N.C. N.O.
Power off or P.S. failure
OFF
OFF
OFF
X
O
X
O
Power on in normal condition
ON
OFF
OFF
O
X
X
O
Power on in Overtemp condition
ON
ON
OFF
X
O
X
O
Power on & Ride-Thru Active
ON
OFF
ON
O
X
O
X
NOTES:
X = contact is closed under stated conditions
O = contact is open under stated conditions
4.2.2. I
NDICATORS
4.2.2.1. ASB
3534R2
C
ONTROL
B
OARD
The ASB 3534R2 is the main control board of the Ride-Thru Control
module used in all 20 Amp M3534R Ride-Thru Control Modules. Figure
4-2 shows the locations of all major components of the board, which are
described in detail below.
Figure 4-2: ASB 3534R2 RTM Control Board Features
Dwg: 120215 Rev: 20120621