User’s Manual
37
S
YMPTOM
A
CTION
Ride-Thru Active output
does not close or
Attached Drive Trips
during power quality
events
▪
Check Enable Input.
▪
Check Ride-Thru Ready output.
▪
Check Precharge Complete output.
▪
Check IGBT fuses.
▪
Verify Ride-Thru is connected to the attached drive.
▪
Initiate Test Mode to ensure Ride-Thru is operating properly.
Input Undervoltage
output is open
▪
Check the DC input voltage.
▪
Check jumpers on the 3460M6 board.
Blown Fuse light is ON
▪
Check IGBT fuses.
DD5 display shows AC
voltages 2x greater than
what is correct or DC
voltages and DC
currents are zero
▪
Check the polarity of the 15V wires going to the current sensors.
CAUTION!
R
EPAIRS OR MODIFICATIONS TO THIS EQUIPMENT ARE TO BE PERFORMED
BY
B
ONITRON APPROVED PERSONNEL ONLY
.
A
NY REPAIR OR MODIFICATION
TO THIS EQUIPMENT BY PERSONNEL NOT APPROVED BY
B
ONITRON WILL
VOID ANY WARRANTY REMAINING
.
5.4. T
ECHNICAL
H
ELP
–
B
EFORE
Y
OU
C
ALL
If possible, please have the following information when calling for technical help:
•
Exact model number of affected units
•
Serial number of unit
•
Name and model number of attached drives
•
Name of original equipment supplier
•
Brief description of the application
•
The AC line to line voltage on all 3 phases
•
The DC bus voltage
•
KVA rating of power source
•
Source configuration Wye/Delta and grounding
This information will help us support you much more quickly. Please contact us at
(615) 244-2825 or through www.bonitron.com
Summary of Contents for M3460UC
Page 6: ...M3460 6 This page intentionally left blank ...
Page 18: ...M3460 18 Figure 3 2 M3460UC POWER Terminal connection ...
Page 38: ...M3460 38 This page intentionally left blank ...
Page 43: ...User s Manual 43 Figure 6 2 M3460 E2 Enclosure Dimensional Outline ...
Page 44: ...M3460 44 Figure 6 3 M3460 E4 Enclosure Dimensional Outline ...
Page 52: ...M3460 52 This page intentionally left blank ...
Page 53: ...User s Manual 53 NOTES ...
Page 54: ...M3460 54 This page intentionally left blank ...