12.4.5
0x3004/0 Boolean Mux
Index Sub-index
Meaning
Data type Access Map Def.-Val
0x3004
0
Boolean Mux
Unsigned16
ro
Tx
Via object 0x3004 up to 16 boolean values can be transferred from the ACU to a PLC
in a compressed manner. Each bit in 16 bit object 0x3004 displays the actual value of
the connected boolean source.
Bit number 0 … 15 corresponds with index number 1 … 16!
The sources for the 16 bits can be chosen from a choice list via the index parameter
CANopen
®
Mux Input.
1422. Parameters 1420 and 1421 are the associated write
and read parameters which you have to set prior to writing/reading parameter 1422.
By using VTable this process is easier and more clearly laid out.
For writing and reading index parameters refer to chapter12.3.2 “Handling of index
Default value is 7 – Off.
Example:
COB ID CB Index SI Data
Read Request
601
40 04 30 00 00 00
Reply
581
4B 04 30 00 03 00
CB: Control byte SI: Sub Index All values in hexadecimal without leading 0x
88
CM-CAN ACU
04/13