14.3.3
Reference value / actual value
The PLC gives its reference value to the frequency inverter via object
in the RxPDO used and receives the information on its actual value back via
in the TxPDO used.
The use of the reference/actual value channel depends on the set configuration (con-
trol system). The actual value is generated from the appropriate source depending on
the control system used.
and the actual value in object
are interpreted in the notation RPM. Conversion into a fre-
quency (reference value), or from a frequency (actual value) is carried out in the fre-
quency inverter.
The reference value for the frequency inverter from object
connected to the reference line value. This reference value is combined with the in-
ternal reference value from the reference frequency value channel in the input of the
ramp function. Reference frequency value channel: see operating instructions.
The internal reference value from the reference frequency value channel and the ref-
erence line value can be fed to the ramp individually or as an added variable. Setting
is carried out via the data set change-over capable parameter
Ramp setpoint
434.
Parameter
Setting
No.
Description
Min.
Max.
Fact. sett.
434 Ramp setpoint
1
3
3
Operation mode
Function
1 - Internal reference
frequency value
Reference value from the sources of the reference fre-
quency value channel
2 - Reference line value Reference value via a communication interface
3 -
Internal reference
frequency value +
reference line value
Sum of internal reference frequency value and reference
line value
This function is only relevant for non motion control configurations (Parameter
Con-
figuration
30 ≠ x40)
04/13
CM-CAN ACU
175