12.5.16
0x6066/0 Following error time out
Index Sub-index
Meaning
Data type Access Map Def.-Val
0x6066
0
Following error time out
Unsigned16
rw
No 0xA
(=10)
Object works in:
•
o
All modes
Object doesn’t work in:
•
Non motion Control (conf.
≠
x40)
When a following error (Object
) occurs longer than the
defined value of object 0x6066
following error time out given in milliseconds, the corre-
sponding bit in the Status word (bit 13
following error) is set to one. No device fault is
triggered.
Writing to object
following error time out automatically generates a write command to
parameter
Contouring Error Time
1119 (data set 5, all data sets in RAM only !).
If object 0x6066/0 was written and then a save parameters command (object
processed, the object value is stored in non-volatile memory.
After the next power on of the inverter, the previously set value is reactivated and
overwrites the setting of
Contouring Error Time
1119.