Orion ISS
This Installation Manual provides instructions on how to mount the S2000-AR8 Addressable
Eight-Input Module (hereinafter referred to as the module) and get it ready for operation.
To get information on module’s description and rules of settings and operation please refer to
its User’s Manual, which can be found online at
http://bolid.ru
in the section PRODUCTS.
1 SAFETY PRECAUTIONS
-
The module contains no circuits under hazardous voltages.
-
The design of the module meets the requirements of electric and fire safety in
accordance with Russian standards GOST 12.2.007.0-75 and GOST 12.1.004-
91.
-
The design of the module provides its fire safety in case of emergency operation
and on violations of operation rules as per
GOST 12.1.004-91.
-
Do shut off power from the polling loop controller prior to mounting,
installing, and maintaining the module.
-
Installation and maintenance shall be carried out by personnel qualified for the
Electrical Safety of Level II or higher.
2 MOUNTING THE MODULE
2.1 The S2000-AR8 is to be installed on a wall or within a cabinet at a place protected against
atmospheric precipitations, mechanical damages, and unauthorized access.
2.2 The S2000-AR8 should be mounted in line with Regulatory Document
РД
78.145-92
“Rules for Performance and Acceptance of Works. Fire and Intrusion Alarm Installations”. If
the S2000-AR8 is housed in unwatched premises it should be located at least 2.2 m higher
than the floor level.
2.3 The module is to be wired as shown in Figure 6.
Addressable Eight-Input Module
S2000-AR8
Installation Manual