MK-2 RECESSED MOUNTING KIT
INSTRUCTION MANUAL
1
TECHNICAL DATA
1.1
General
MK-2 Recessed Mounting Kit is used to secure a smoke or heat Bolid detector DIP-34A-03, DIP-34A-04, DIP-34PA-03, S2000-IP-03, or
S2000-IP-PA-03 to a suspended ceiling tile. Please refer to the manual of the relevant detector for detector descriptions and installation and
operation instructions.
1.2
Specifications
1.2.1
Overall dimensions:
-
Outer diameter: 130 mm.
-
Inner diameter: 102 mm.
-
Height: 116 mm.
1.2.2
Cut-out diameter: 106 to 116 mm.
1.2.3
Weight: 0.1 kg max.
1.2.4
Content of precious materials: not subject to inventory accounting in case of
storage, disposal and recycling (Clause 1.2 of Russian Standard GOST
2.608-78).
1.3
Standard Delivery
MK-2 Mounting Kit (including two self-tapping screws 4
×
10)
−
1 pc.
Instruction Manual
−
1 copy
Packing
−
1 pc.
2
OPERATION INSTRUCTIONS
2.1
MOUNTING
2.1.1
The MK-2 is to be secured into the suspended ceiling by means of hold down brackets (see 1 below).
Select the place on the ceiling to secure the detector.
Then cut out a 106mm to 116mm diameter hole in the intended
area.
Pass the wiring through the mounting hole. Insert the detector
mounting base into the flange aligning the longer match mark on
the base with the longer match mark on the flange.
Align the slotted holes of the base with holes on the flange,
insert screws provided into holes, and fix the base into the flange.
Lift the spring brackets vertically and holding them in this
position insert the flange into the mounting hole; then release the
brackets. Connect wiring to the terminals as per the project design and
as described in the detector instruction manual.
2
×
self-tapping screw 4
×
10
flange