FOCUS
1.4
Settings
Page 14
BOGE FOCUS compressor control for piston compressors
Set parameters
1. Opening of the parameter list by means of the desired code (user code,
service code, BOGE code).
2. If the cursor points at the parameter which is to be changed, e.g. maximum
pressure in the pressure range 1 (P012), this selection is acknowledged
by actuating the
ENTER key
.
3. If a digit (e.g. 130 psi) is blinking on the right side of the parameter, the de-
sired value can be set (e.g. 145 psi) by actuating the
/
keys
.
4. By actuating the
ENTER key
this input is acknowledged and stored.
Actuating the
INFO key
at this place causes a leaving of the setting
without accepting the changes.
You can proceed with every parameter in the same way.
Parameters
The setting of the parameters can be accomplished as described above (see
also parameter list).
P001 Language
The following display languages are available:
German (DE), English (GB), Italian (IT), Russian (RU), Finnish (FI),
Danish (DK), Lithuanian (LT), Swedish (SE), Polish (PL), Spanish (ES),
Portuguese (PT), French (FR), Dutch (NL), Latvian (LV), Turkish (TR),
Czech (CZ), Hungarian (HU).
P012 p
max
Pressure range 1
Pressure range 1 is the default pressure setting for the compressor.
Here the upper pressure target value for pressure range 1 is set. As soon as
the net pressure has reached
p
max
the compressor changes from load run to
idling.
P013 p
min
Pressure range 1
Pressure range 1 is the default pressure setting for the compressor.
Here the bottom pressure target value for pressure range 1 is set. If the com-
pressor is in the Ready state and the net pressure drops below
p
min
, the com-
pressor starts with the output.
P014 p
max
Pressure range 2
Pressure range 2 offers the possibility for pressure decreases and the value
must not be set above that of pressure range 1.
Note!
If
p
max
is set so that
p
min
is larger or the minimum hysteresis (P011) is not
complied with, confirming it with the
-key will force you to edit P013.
Note!
If the pressure range selection is effectuated by a master control or the exter-
nal contact you have to observe when setting the pressure ranges, that in
case of a power failure or fault of the master control, the compressor control
eventually falls back on this pressure range.