BOGE FOCUS compressor control for piston compressors
Page 11
FOCUS
1.3
Display information
Info # 2
The information to the control settings as master control resp. the current sta-
tus of the integrated timer are displayed here.
The priority sequence is only displayed if the number of compressors in the
base load switch control is above 1. In case the number of compressors is set
to 1, n / a is displayed here.
The display of the priority sequence shows the currently effective sequence for
selecting the compressors. Depending on the setting the priority sequence
is changed cyclically (base load switch control) or selected by means of the
switch clock.
For each parameterized compressor the current output signal status, the cur-
rent priority level and the time until the next priority change, with switched-on
base load switch control, is displayed. If only the switch clock is active (cyclic
changing time set to 0) no time is displayed.
Meaning:
C1 C2 C3 means, that the compressors 1–3 are connected and the sequence
1, 2, 3 is chosen – in this case none of the compressors receives an output
signal.
C1
C3 C2 means as in the first example, that the compressors 1–3 are param-
eterized although they are selected in the sequence 1, 3 and 2. Furthermore,
compressor 1 receives an output signal in this case.
The output signal status is shown by means of a black background in the graph-
ical presentation of the compressors in the display
.
Date / Time
This menu page shows the current setting of the real-time-clock.
The time is displayed in hours, minutes and seconds and the date with day of
the week, day, month and year.
In case of a switched-off power supply the real-time-clock is operated by its
battery – provided the plug-in jumper contacts arranged next to it are connect-
ed and their voltage is sufficient (see also chapter Maintenance).
Pressure range
Activated pressure range
System pres-
sure / net pres-
sure
Shows the current system pressure / net pressure.
Switch clock
–
A-Z active timer channel
–
n / a no channel active
Priority se-
quence (time
until change
of priority)
Set priority sequence, active compressors and time in h and min until
next change of priority.
Note!
Changes to the displayed data have to be accomplished by means of the
base load switch control (see also chapter
)
or switch
clock settings.