Servicing and maintenance
6.3
Having maintenance work performed at fixed servicing intervals
Page 66
BOGE Operating instructions for scroll compressors, series EO 6...EO 22 D
Have the function of the safety valve checked exclusively by BOGE Service
personnel.
Interval: After approx. 3,000 operating hours but at least once a year.
Every 3,000 operating
hours / annually:
Checking the V-belts
Check the V-belts:
–
After approx. 3,000 operating hours but at least once a year for damage,
correct tension and alignment.
Every 3,000 operating
hours / annually:
Checking the non-return
valves
Check the function of the non-return valves on the scroll units:
–
After 3,000 operating hours but at least once a year.
Every 5,000 /
10,000 operating hours:
Scroll compressor
servicing
10 bar compressor:
After 5,000 operating hours but after two years at the
latest.
8 bar compressor:
After 10,000 operating hours but after four years at
the latest.
Have the following maintenance work on the scroll compressors carried out
exclusively by BOGE Service personnel.
The following work must be carried out:
–
Replace "Tip Seal" sealant on scroll compressor
–
Service / lubricate scroll compressor bearing
–
Clean cooling fins on scroll compressor
Every 10,000 operating
hours: Replacing the
V-belts
Replace the V-belts:
– If visibly damaged.
– After 10,000 operating hours.
Replacing the V-belts:
1. Switch off the compressor using the OFF button.
5. Remove the service side cladding.
WARNING
Risk of injury due to sharp edges, hot surfaces, overpressure and
exposure to dust!
This maintenance work should only be carried out by authorised and quali-
fied personnel.
Î
Wear PPE.
Prior to the maintenance work:
2. Open the mains disconnecting device and secure it to prevent it being
switched on again.
3. Allow all hot compressor components to cool to 50°C.
4. Depressurise the system.