BOGE compressor control airtelligence provis 3
Page 9
Assembly and connection
3.1
Installation of the control
Part 3: Assembly and
connection
3.1 Installation of the control
The
airtelligence provis 3
is installed in a separate switch cabinet. The oper-
ating unit of the control, the touch panel (1), is located in the front of the switch
cabinet (2).
Fig. 3.1: Switch cabinet with touch panel
After delivery, the switch cabinet must be set up and installed at a suitable
location before the necessary components can be connected and the control
can be put into operation.
Assembling the switch
cabinet
Safety instructions prior to assembly
– Ensure that the installation site is free from dirt and moisture.
– Physically separate the switch cabinet from frequency converters and
high-voltage appliances.
– Avoid functional failures that can be caused by heat generation and inter-
ference with adjacent components, by meeting the requirements of EN
61439:
–
Ensure that the temperature limits at the place of operation are
observed (see „8.1 Technical data“, page 75).
–
Do not place the switch cabinet directly next to heat sources.
–
The components are designed for cooling by convection: therefore
avoid heat accumulation and ensure that no openings are covered
(e.g. by surface-mounted cables).
– During assembly, ensure that the bottom side of the control cabinet hous-
ing points downwards (see also „Housing dimensions and component
overview“, page 76). The specified ambient conditions, especially the
ambient temperatures, apply to this alignment only.