background image

 

 

 

3. MOUNTING INSTALLATION 

3.1 

CEILING MOUNTING 

 

IMPORTANT!

 Ensure that the ceiling is capable of taking the weight of the heater. 

For  optimum  results  do  not fit  in ceilings  higher  than  3m.  Air  is  taken  in  through the large  grille  and discharged  through the  smaller  grille.  The  air 
intake  and  discharge  areas  must  be  kept  completely  clear  for  a  minimum  of  1.5m  from  the  front  of  the  heater.  In  an  area  using  multiple  units, 
heaters should be spread to provide an even heat distribution. 
Remove the front grille / cover by undoing the 8 screws securing it in place (You d

on’t need to remove this cover if using M6 drop rods or hanging hooks.) 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Using the drawing above mark out the holes required to secure the heater case to the ceiling. Use the 4 x keyhole slots and an additional 2 holes (at 
least one each side) once installed to lock the heater in place. 

These additional 2 holes MUST be used to stop the possibility of the case sliding off its Keyhole fixings. 

Secure to the ceiling using suitable fixings (not supplied). It will be easier to do some of the electrical connections before finally securing to the ceiling. 

3.2  DROP ROD MOUNTING 

The heater has 4 x M6 threaded holes and 4 x M10 keyhole holes suitable for using M6 or M10 drop rod studding. If using M6 threaded holes fully 
screw the studding into each hole and use a lock nut to stop it rotating and coming out. If using M10 studding a nut must be placed and tightened 
above and below the case on each of the 4 studs to hold the case securely to the M10 drop rods (Removal of the grille / guard will be needed so 
you can add an M10 Nut inside the heater). Use the diagram above to determine the spacing of the drop rods. If you use drop rods you should be 
able to gain access to all the electrical connections after you mount the heater. 

 

4.  ELECTRICAL CONNECTIONS 

4.1  230V SINGLE PHASE 

– Without controls. 

Please make sure you have read the Safety instructions and that you are a suitably qualified electrician before continuing. 
Drawings show connections inside the black terminal box on the outside of the heater. 

Do NOT use power tools to undo or do up terminal screws.

 

Please Note:- Specified cable sizes are for typical installations, correction factors may need to be used when determining actual cable sizes. 
 

Standard Connection and Use 
Use 1.5mm² 3 Core Mains Cable (see note above). 
Connect Brown wire 

– Terminal 1 or L. 

Connect Blue wire 

– Terminal 5 or N. 

Connect Green / Yellow wire 

– Terminal E or 

Ensure the link 

 is in position in the Power Supply Box as 

shown  in  drawing  to  the  left.  Link  should  be  between  terminals  2 
and 3. 

Ensure  the  3  links 

  are  in  position  in  the  Control  Box  as 

shown  in  drawing  to  the  left.  Links  should  be  between  terminals  1 
and 2, 3 and 4, 4 and 5. 
 

If you wish to de-rate the heater from 3kW to 2kW remove the link 

between terminal 3 and terminal 4 in the Control Box. 

DO NOT REMOVE ANY LINK IN THE POWER SUPPLY BOX.

 

Ensure  you  tighten  up  the  screws  after  removing  the  link.  See 
drawing to the right. 

PLEASE CHECK ALL CONNECTIONS BEFORE TURNING ON AS INCORRECT WIRING IS NOT COVERED BY THE GUARANTEE

 

 

Reviews: