CONTROLS/ACCESSORIES
A remote switch module is supplied as standard with the
HCA door curtain. A wiring diagram is enclosed with these
instructions and should be studied prior to installation.
Remote Switches
The remote switch module provides on/off, high fan/low fan
and high heat/low heat settings. It is not possible to select
low fan/high heat as overheating may occur. The module is
supplied loose for on-site fitting. Remote wiring is not
provided by BN Thermic.
Over Temperature Protection
Two thermal switches are fitted. One thermal switch
provides the fan over-run. The fan will either continue to run
after the unit is switched off until the air temperature in the
casing drops below 50°C or will switch the fan back on after
the unit is turned off should the case temperature rise
above 50°C for a short period. The other manual reset
thermal switch provides the safety cut out. If the air
temperature in the casing rises above 60°C this will cause
the safety cut out to trip. The safety cut out can be reset by
pressing the red button located on top of the unit. If the
safety cut out trips regularly; check the operation of the fan
and that the airflow through the unit is not restricted by dust
and the inlet or outlet are not obstructed. If the problem
persists please contact BN Thermic.
Wall Hanging Bracket
All models come complete with a hanging plate for vertical
wall surface mounting.
Remote switch module
Electric heating
elements
Motor/electrical connection
enclosure