25
Shenyang Bluelight Automatic Technology Co., Ltd.
BL6-DU20PX series Integrated Door Motor Controller User Manual
Chart 6.1 F0 Basic Function Parameter (Cont’d)
Para
Name
Range
Default
Min
Unit
Description
F003
Panel
Running
Speed
Slope
0~F104
0.5Hz
0.01
Hz
In panel control mode, press” UP” or “Down”
to increase or decrease the motor speed
frequency.
F004
Low Speed
Setting
0~F104
4.00Hz
0.01
Hz
Speed to set when slow speed close door
function is valid.
F005
Carrier
Frequency
5.0kHz
~12.0k
Hz
8.0kHz
0.1Hz
Adjust the carrier frequency to reduce the
motor noise, keep away from the resonance
points in the mechanical system, and reduce
the leakage current in circuits and interference
generated by the controller.
Lower carrier frequency leads to high
secondary harmonic component, more motor
loss, and higher motor temperature.
Higher carrier frequency makes lower motor
loss and lower motor temperature, but higher
controller
loss
and
higher
controller
temperature.
6.2
F1 Motor Parameter
Chart 6.2 F1 Motor Parameter
Function
Code
Name
Setting Range
Min Unit
Factory
Default
Setting
F100
Motor Type
1: Asynchronous 0: Synchronous
1
1
F101
Motor Pole
0~100
1
6
F102
Motor Rated
Frequency
0~99.99Hz
0.01Hz
50.00Hz
F103
Motor Rated Power
0~750W
1W
500W
F104
Motor Rated Speed
0~9999rpm
1
940rpm
F105
Motor Back EMF
0~999V
1
280V
F106
Motor Phase
Inductance
0.00~99.99mH
0.01
16.1mH
F107
Motor Phase
resistance
0.00~99.99mΩ
0.01
2.4mΩ
F108
Motor Rated
Current
0.000~9.999A
0.001A
1A
F109
No-load Current
0.000~9.999A
0.001A
0.6A
F110
Slip Frequency
0.000~9.999Hz
0.001Hz
3.000Hz
F111
Motor Rated
Voltage
0~220V
1V
50V
Note:
1. Please set the parameters according to the nameplate.
2. Please select the proper motor according to the system for higher performances. If the
difference between motor power and the standard adaptive motor is too large, the system control