507768-02B
Page 21 of 56
Issue 1904
Maximum Allowable Exhaust Vent Lengths with Furnace Installed in a Closet or Basement Using Ventilated Attic or Crawl
Space for Intake Air in Feet
Standard Termination at Elevation 0 - 4,500 ft
Number of
90° Elbows
Used
2" Pipe
2-1/2" Pipe
3" Pipe
Capacity
Capacity
Capacity
045
070
090
110
045
070
090
110
045
070
090
110
1
66
51
29
9
95
95
73
38
113
112
93
93
2
61
46
24
4
90
90
68
33
108
107
88
88
3
56
41
19
n/a
85
85
63
28
103
102
83
83
4
51
36
14
80
80
58
23
98
97
78
78
5
46
31
9
85
75
53
18
93
92
73
73
6
41
26
4
70
70
48
13
88
87
68
68
7
36
21
n/a
65
65
43
8
83
82
63
63
8
31
16
60
60
38
3
78
77
58
58
9
26
11
55
55
33
n/a
73
72
53
53
10
21
6
50
50
28
68
67
48
48
Standard Termination Elevation 4,501 - 10,000 ft.
Number of
90° Elbows
Used
2" Pipe
2-1/2" Pipe
3" Pipe
Capacity
Capacity
Capacity
045
070
090
110
045
070
090
110
045
070
090
110
1
66
51
29
n/a
95
95
73
38
113
112
93
93
2
61
46
24
90
90
68
33
108
107
88
88
3
56
41
19
85
85
63
28
103
102
83
83
4
51
36
14
80
80
58
23
98
97
78
78
5
46
31
9
85
85
53
18
93
92
73
73
6
41
26
4
70
70
48
13
88
87
68
68
7
36
21
n/a
65
65
43
8
83
82
63
63
8
31
16
60
60
38
3
78
77
58
58
9
26
11
55
55
33
n/a
73
72
53
53
10
21
6
50
50
28
68
67
48
48
* Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and
Exhaust must be same pipe size.
* Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length
calculation.
Table 5C.
Summary of Contents for BG961UHE
Page 3: ...507768 02B Page 3 of 56 Issue 1904 Figure 1 Parts Arrangement ...
Page 22: ...507768 02B Page 22 of 56 Issue 1904 Figure 25 Figure 26 ...
Page 37: ...507768 02B Page 37 of 56 Issue 1904 Figure 59 Trap Drain Assembly Using 1 2 PVC or 3 4 PVC ...
Page 43: ...507768 02B Page 43 of 56 Issue 1904 Figure 67 Typical Wiring Diagram ...