HOTPLATE FLANGE
GASKET
WELLSLOK
COUNTERTOP
SCREWDRIVER
21.7
14 AWG Cu
10
90°C
10.8
10.8
18.8
5200
240
H-636
METAL SHIELD
90°C
10
14 AWG Cu
18.8
9.4
9.4
16.3
3900
208
H-636
16.7
8.3
8.3
14.4
4000
UNIT MUST BE INSTALLED IN AN ALL METAL COUNTER
INSTALLATION INSTRUCTIONS
THE INSTALLATION OF RECOGNIZED COMPONENT UNITS REQUIRES
ADDITIONAL EVALUATIONS TO UNDERWRITERS LABORATORIES
STANDARDS.
INSTALLER MUST MEET CONDITIONS OF ACCEPTABILITY OUTLINED
BELOW UPON INSTALLATION:
1. This appliance must be installed in an all metal counter with suitable
wiring and control enclosures conforming to national and local electrical
codes.
2. Electrical component temperatures, including wiring, within and
surrounding the appliance must be monitored in the end use installation
for suitability.
3. Electrical grounding of all dead metal parts must be reliably
connected to the grounding means of the appliance and must comply with
requirements outlined in the appropriate Underwriters Laboratories Inc.
classification, national and local electrical codes.
4. Increased clearances are required if storage of combustible materials
is in close proximity to this appliance.
5. Unit shall be accessible for servicing from bottom.
6. The name/rating plate information shall be accessible.
TO FABRICATE AND INSTALL:
1. Lay out cutout dimensions on countertop and control
apron as shown in cutout details.
2. Cut and/or drill holes as required in countertop and apron.
3. Place gasket on underside of flange (see detail above).
4. Locate Hotplate over counter to cutout. Pass control panel
through countertop cutout and bring it through control cutout
on apron. Seat Hotplate on countertop.
5. From underneath, insert screwdriver into slots on patented
Wellslok frame and twist ears counterclockwise to secure
flange tightly to countertop.
6. Mount control box to apron using screws supplied. Connect
service leads to terminal block located at right of control
box. Mount front panel to control box.
NOTE: INSTALLATION MUST MEET LOCAL AND NATIONAL
ELECTRICAL CODES.
UNIT TO THE NEAREST SURFACE
SUGGESTED CLEARANCE FROM
1
(25)
9
(229)
(51)
2
1
(25)
FRONT
BOTTOM
SIDE
BACK
CLEARANCES
PRODUCT DIMENSIONS
CUTOUT DETAILS
ELECTRICAL
WELLS/BLOOMFIELD * VERDI, NV
MODEL H-706, H-636
INSTALLATION INSTRUCTIONS
37118-1 REV (-)
BUILT-IN HOTPLATES
PHASE
AMPS
7.2
7.2
L3
L2
L1
90°C
90°C
14 AWG Cu
14 AWG Cu
14.4
12.5
3000
208
240
H-706
H-706
RATING
FIELD WIRING GAUGE
TEMP.
SINGLE
AMPS PER LINE 3 PHASE
WATTS
VOLTS
MODEL
10
10
3 PHASE
1 PHASE
90°C
10
-
16.7
-
H-706EU
220-240
4000
-
-
9
(229)
13 3/4
(349)
2 13/16
(71)
4 7/8
(124)
22 7/16
(570)
1 1/2
(38)
12 3/4
(324)
23 1/2
(597)
4 1/2
(114)
14 3/4
(375)
14 1/8
(359)
6 1/4
(159)
INCHES
(MM)