background image

180-CL2118.IPI.1 v1.00

August 5, 2020

Page 57

CL2118.IPI.1

TROUBLESHOOTING

Please check to make sure the instructions are followed exactly before attempting trouble shooting of the appliance.

TROUBLESHOOTING AND SERVICING OF GAS AND ELECTRICAL DEVICES OF THE APPLIANCE 

SHOULD ONLY BE CONDUCTED BY A QUALIFIED SERVICE TECHNICIAN

.

PROBLEM

POSSIBLE CAUSE

ACTION

Thermostat does not work

The pilot flame has gone out

The On/Off switch is turn to OFF

• 

Turn it ON

The thermostat is set too high

• 

The thermostat is set too high

No spark generation

Spark develops near the 

pilot assembly or could occur 

onboard

• 

Check pilot assembly wiring

• 

Check for broken or poor connection from the sparker to 

the electrode

• 

Check for the spark shorting or arcing at other locations

• 

Check for defective sparker and spark electrode

No pilot flame ignition

No spark from the igniter

• 

See “no spark generation”

Air in the gas line

• 

It takes a while for all the air to purge out of the pilot before 

gas can reach the pilot and ignite

Pilot gas pressure dropout upon 

main burner gas valve opening

• 

Check gas mains supply and pressure

No gas flow out of the pilot 

burner

• 

Check gas valve wirings and connections to the board

• 

Check the pilot burner for obstruction

• 

Check the wirings and connections between the pilot 

assembly and the board

• 

Check the correct gas type settings on the valve and pilot 

burner assembly orifice

Pilot will not remain lit

Problem with Flame Sensor 

circuit

• 

Check for proper connection of the Flame Sensor to the 

IFC board

• 

Check pilot for full flame impingement around Flame 

Sensor

• 

If flame is too small, check gas pressure, adjust pilot rate 

screw, check pilot head for damage

• 

Ensure the ground wire is properly attached to the pilot 

mounting bracket and that it is makes a good electrical 

connection.

Restrictor setting

• 

Use the correct restrictor setting for the venting 

configuration

Remote control does not work

The pilot light has gone out

• 

See “Pilot will not remain lit”

The remote is too far away from 

the heater

• 

Use the remote closer to the heater

One of the remote control 

batteries are dead

• 

Replace the batteries

No reaction to command

IFC or transmitter batteries are 

low

• 

Replace the batteries

A maximum number of failed 

ignitions or flame restorations 

have been reached

• 

Remove any possible blocking conditions. See “locking 

conditions”

• 

See how to reset the board from Lockout

No communication between the 

remote control and the IFC

• 

Reprogram the transmitter to the IFC.

• 

Follow the initializing system for the first time

Summary of Contents for CLARITY CL2118.IPI.1

Page 1: ...ual with the homeowner Homeowner Please keep these instructions for future reference Pour la version française de nos manuels S V P vous référez à notre site web www blazeking com OPERATION INSTALLATION MANUAL WARNING If the information in these instructions are not followed exactly a fire or explosion may result causing property damage personal injury or loss of life Date Installed ____________ S...

Page 2: ...ON PLANNING_______________________________________________________________________________ 23 PRECAUTIONS 23 FRAMING ROUGH OPENING 23 FRAMING CORNER INSTALLTION 24 WALL FINISH 25 CRACKING WALL FINISHES 26 INSTALLATION__________________________________________________________________________________________ 27 HARD WIRING CONNECTION 27 OPTIONAL S Z5216 IPI BLOWER CONNECTION 28 INITIAL SETUP 30 VENT...

Page 3: ...lified service person The appliance should be inspected before the first use and at least annually by a qualified service person More frequent cleaning may be required due to excessive lint from carpeting bedding material etc It is imperative the control compartments burners and circulating air passageways of the appliance be kept clean If the CLARITY CL2118 is pulled out of its installation and t...

Page 4: ... B149 1 in Canada A manufactured home USA only or mobile home OEM installation must conform with the Manufactured Home Construction and Safety Standard Title 24 CFR Part 3280 or when such a standard is not applicable the Standard for Manufactured Home Installations ANSI NCSBCS A225 1 or Standard for Gas Equipped Recreational Vehicles and Mobile Housing CSA Z240 4 Always connect this gas appliance ...

Page 5: ...This appliance is certified for installation in a bedroom or a bedsitting room This appliance is only for use with the type of gas indicated on the rating plate and may be installed in an aftermarket permanently located manufactured mobile home where not prohibited by local codes This appliance is not convertible for use with other gases unless a certified kit is used Only for direct discharge wit...

Page 6: ...aux de verre seulement être fait par une personne qualifiée À utiliser uniquement avec le numéro de pièce de barrière 645 1821 Aussi pour l usage dans les maisons mobiles manufacturées après que la maison soit installée sur le site Pouvant être converti pour usage avec le gaz naturel ou le propane comme suit Pour le gaz naturel une fois équipé d un orifice 39 Pour le propane une fois équipé de l o...

Page 7: ...ON TO APPEAR ON THE GLASS THIS IS A NORMAL OCCURRENCE AS YOUR APPLIANCE HEATS UP CLEARANCE TO COMBUSTIBLES Side of unit to sidewall 4 102 mm Back of unit to back wall 4 102 mm Corner of unit to sidewall 4 102 mm Top of unit to ceiling top vent rear vent with snorkel 32 813 mm Top of unit to ceiling 2 0 up and out vent 45 1143 mm Vertical Vent 1 25 mm from outside surface Horizontal Vent 13 330 mm ...

Page 8: ...gas control which has been under water LIGHTING INSTRUCTIONS 1 STOP Read the safety information above 2 Set the thermostat to the lowest setting 3 Turn off all electric power to the appliance 4 Do not attempt to light the pilot by hand 5 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the safety information above If you don t s...

Page 9: ...N OFF solenoid EV1 terminals 2 ON OFF solenoid EV2 terminals 3 Inlet pressure test point 4 Outlet pressure test point 5 c Electrical pressure modulator device 6 Pressure modulator device terminal 7 Pilot adjusting screw 8 Pilot outlet 9 Gas inlet with protective seal 10 Gas outlet with protective seal 11 Ground connection 12 Mounting holes ...

Page 10: ...ed to turn on off or index through Thermostat functions Fig 1 2 Additionally a Key Lock feature is provided Fig 19 page 15 An optional kit S 0900 is available to allow the unit to be controlled via smart phone app It includes a wireless dongle harness and upgraded proflame connect transmitter remote THE TRANSMITTER AND RECEIVER ARE RADIO FREQUENCY DEVICES PLACING THE TRANSMITTER IN OR NEAR METAL M...

Page 11: ...he mounting hardware supplied with the remote control Insert the remote control onto the adapter Fig 4 OPERATING PROCEDURE Initializing the System for the First Time Power the IFC control Install the 3 AAA type batteries in the Transmitter battery bay located on the base of the Transmitter Fig 5 With the batteries already installed in the Transmitter push the red sync button on the IFC control Nex...

Page 12: ... temperature Fig 8 At the same time the Receiver will turn off the appliance A single beep from the Receiver confirms reception of the command Remote Flame Control The proflame has six 6 flame levels With the system on and the flame level at the maximum in the appliance pressing the Down Arrow Key once will reduce the flame height by one step until the flame is turned off The Up Arrow Key will inc...

Page 13: ... temperature is displayed on the LCD screen of the Transmitter Fig 11 Smart Thermostat Transmitter Operation The Smart Thermostat function adjusts the flame height in accordance to the difference between the set point temperature and the actual room temperatures As the room temperature gets closer to the set point the Smart Function will modulate the flame down To activate this function press the ...

Page 14: ...to the blower control icon Fig 13 Use the Up Down Arrow Keys Fig 1 to turn on off or adjust the blower speed Fig 14 A single beep will confirm reception of the command Fig 13 Fig 14 Remote Auxiliary Relay Control The auxiliary function controls the AUX relay outlet To activate this function use the Mode Key Fig 1 to index to the AUX icon Fig 15 16 Pressing the Up Arrow Key will activate the outlet...

Page 15: ...he reception of the command Fig 17 Fig 18 Key Lock This function will lock the keys to avoid unsupervised operation To activate this function press the MODE and UP Keys at the same time Fig 19 To de activate this function press the MODE and UP Keys at the same time Low Battery Power Detection The life span of the remote control batteries depends on various factors quality of the batteries used the...

Page 16: ...FACES Painted powder coated or porcelain enameled surfaces should be wiped with a damp cloth periodically Ensure the appliance has cooled down completely before any cleaning Do not use other cleaners as they may leave a residue which can become permanently etched into the surface CLEANING THE GLASS DO NOT TO CLEAN THE GLASS WHILE IT IS HOT One of the by products of combustion and moisture in the f...

Page 17: ...be removed 1 Turn off the appliance and allow it to cool down completely 2 Lift the face trim up and out away from the appliance and set it aside Fig 1 3 Lift the safety screen up and out away from the appliance and set it aside Fig 2 4 There are two door latch mechanisms on top of the glass door Fig 3 Pull the tabs forward and up off the door tabs Fig 1 Fig 2 Fig 3 ...

Page 18: ...st be done by a qualified service technician The glass door must be purchased from a Blaze King dealer No substitute materials are allowed BURNER REMOVAL 1 Turn off the appliance and allow it to cool down completely 2 Remove the face trim safety screen and glass door see GLASS DOOR REMOVAL on previoius page 3 Remove the glass floor plate and set it aside Fig 5 4 Remove the floor plate assembly and...

Page 19: ...urn off the appliance and allow it to cool down completely 2 Remove the face trim and safety screen by lifting up and out see GLASS DOOR REMOVAL 3 Slide the safety screen out of the frame the tabs may have to be adjusted Fig 7 4 Slide the new safety screen in between the frame face and the tabs Ensure screen mesh faces out furthest from glass see image below 5 Hang the safety screen back into posi...

Page 20: ...F CONVERSION KIT CONTENTS The conversion kit contains the following parts S Z0765 LPG 635 OR1 5 1 5 mm orifice 635 977 168 PF2 LP pilot orifice and LPG regulator S Z0766 NG 635 OR39 39 orifice 635 977 166 PF2 NG pilot orifice and NG regulator Conversion Kit labels To convert from NG to LPG or reverse 1 Turn off the appliance and allow it to cool down completely 2 Remove burner see BURNER REMOVAL 3...

Page 21: ...g a 4 mm allen key Fig 9 then screw in the new orifice Fig 10 3 Align the pilot hood with the tab and re attach the pilot hood to the spring clamp 4 Fill out the fuel conversion label and affix between the two labels on the control panel door All valves have been pre set and certified for installation at elevations from 0 4500 feet or 1 1372 m above sea level Fig 8 Fig 9 Fig 10 MAINTENANCE and SER...

Page 22: ...180 CL2118 IPI 1 v1 00 August 5 2020 Page 22 CL2118 IPI 1 MAINTENANCE and SERVICE ...

Page 23: ...be non combustible if they are within the clearances specified The gas line should be run to the right side of the appliance it is also possible to run it to the left side if needed See DIMENSIONS for gas inlet locations Fig 11 This section of the owner s manual is for the use of qualified service technicians only Fireplace placement hearths and venting terminations will be covered as well as the ...

Page 24: ...t u d s 3 6 1 2 9 2 7 m m m i n t o w o o d s t u d s C L E A R A N C E T O C O M B U S T I B L E S FRAMING CORNER INSTALLTION The dimensions for installing the CL2118 appliance in a corner is shown in Fig 12 Do not interfere with the structural integrity of the walls Shown below are minimum clearances increasing these dimensions is allowable as long as vent length remains in the allowable range F...

Page 25: ...ombustible finishing over cement board Additional non combustible material such as tile etc may be applied over top of the cement board or you may choose to leave it finished clean with no tile see next page Be aware that a trim is always required and the trims will accept tile etc behind them up to 1 thick depending on appliance side flange position Additional non combustible finishes if desired ...

Page 26: ...th when drying from a saturated condition Running the fireplace before final finishing will help drive out moisture Always pre drill screw holes through cement board and use screws with self milling head Always use tape over joints Behind joints double up studs or use studs on the flat to add extra support to the joint Adhesive on the backside of wall board behind any joints can help control diffe...

Page 27: ... CONNECTION There are electrical access panels on either side of the Clarity CL2118 IPI for hard wiring power install per local electrical building codes Follow the steps below for running a hard wire power line to the Clarity CL2118 4 Add strain relief to hardwire and junction box Leave approx 6 of line for inside connection 5 Connect ground wire to junction box ground and marrette black and whit...

Page 28: ... out and set to the side 3 Remove the IFC control box from the velcro and bring to front right hand side of the appliance 4 Slide blower through left hand side to the back of appliance Slide wires beneath the valve Ensure wires do not get pinched or hooked anywhere 5 Slide the blower along the back wall until it reaches the stop flange then feed the blower wires underneath the gas supply to the fr...

Page 29: ...ox onto velcro NOTE ENSURE ALL WIRES ARE CLEAR OF BLOWER BLADES 8 Slide label plates back between the IFC control and battery holder 9 Re hang safety screen and face frame if applicable 12 blk 12 white 140 178 619 FAN CONNECTOR X11 150 0721 BLOWER Female 250 NOTE M Spade Connectors supplied with blower ...

Page 30: ...tains the floor glass the other contains the side panels Set glass panels aside in a safe place 4 Remove floor plate assembly from appliance and set aside Fig 14 5 Loosen the top left tab as shown by arrow install the left glass up under the tab and onto the support Fig 15 NOTE THE SIDE WITH LABEL SHOULD BE FACING THE FIREBOX REMOVE BEFORE FIRING Retighten the tab HANDLE GLASS CAREFULLY BY THE EDG...

Page 31: ...ATION RESTRICTIONS In heavy snowfall areas make sure vent termination is located where it will not be blocked by snowfall or snow from snow removal equipment Locate vent termination away from plants bushes or any other object on or near the vent termination that will interfere or obstruct the air flow around it DO NOT recess vent termination into walls sidings or planters Vent terminations located...

Page 32: ...he back sheild from the appliance and discard Fig 20 REAR VENT INSTALLATION Two snorkels are available that can be used in a rear vent application on the CLARITY CL2118 One is the M G Duravent 46DVA H2 SNK36 Fig 18 and the other is the Selkirk 4DT ST36 Fig 19 Fig 18 Fig 19 INSTALLATION Fig 20 ...

Page 33: ...ION 2 Remove upper flue access cover from the appliance and set aside Fig 21 3 Remove the lower flue access cover from appliance and set aside Fig 22 4 Unscrew flue collar from appliance 6 screws Fig 23 Ensure that the sealing gasket is not damaged Fig 21 Fig 22 Fig 23 ...

Page 34: ...0 August 5 2020 Page 34 CL2118 IPI 1 INSTALLATION 5 Rotate flue collar as shown and re install to appliance 6 screws Ensure gasket is seated properly Fig 24 6 Re install the flue access covers discard the back sheild Fig 24 ...

Page 35: ...PPLIANCE S GAS VALVE SUCH DAMAGE IS NOT COVER BY THE MANUFACTURER S WARRANTY Check for proper gas supply pressure by loosening the set screw on supply pressure tap on the gas valve with a small flat tip screw driver and placing a test gauge on the tap Refer to 885 PROFLAME VALVE section The minimum permissible gas supply pressure is 5 0 in w c 1 24 kPa for natural gas and 12 0 in w c 3 0 kPa for p...

Page 36: ...WN TOWARDS THE VENT TERMINATION COULD CAUSE POOR COMBUSTION AND OR HIGH TEMPERATURES THAT MAY PRESENT A FIRE HAZARD Mark a 10 x 10 square around the center mark inside dimensions Cut and frame the exterior wall to accept the wall penetration heat shield Install the penetration shield using wood screws If the wall being penetrated is constructed of non combustible material a 7 hole is acceptable fo...

Page 37: ...l rear vent applications require a listed snorkel termination NOTE Maximum vent lengths may be subject to local codes For best venting performance here are some general venting rules 1 Use only vent systems and components certified for use with this appliance 2 Maintain a minimum of 1 26 mm clearance to combustibles from the outside surfaces of vertical vents and minimum of 1 26 mm from bottom 2 1...

Page 38: ...118 IPI 1 INSTALLATION TYPICAL VENTING EXAMPLES 2 12 8 1 19 26 3 32 CLEARANCE TO COMBUSTIBLES 1 CLEARANCE TO 19 32 12 2 COMBUSTIBLES 26 3 8 2 8 12 45 CLEARANCE TO COMBUSTIBLES 1 19 26 3 15 3 16 TOP VENT VERTICAL 2 0 UP AND OUT REAR VENT WITH SNORKLE ...

Page 39: ...at ceiling install a Box Wall thimble Cut a 10 square hole and frame as shown Fig 25 Ensure all pipe sections are fully twist locked NOTE Always check your local codes before installing venting Necessary clearances and requirements may vary from state to state province to province Through Roof Framing Maintain 10 opening relative to the pitch of the roof Install the flashing with upper portion sli...

Page 40: ...ple 1 V Value 3A 12 1C 3 15 H Value 2B 4 4 V Value Total length of all vertical sections in feet H Value Total length of all horizontal sections in feet Note for H V values for 45º venting see Chart IV elbows are not counted in H or V values vent chart starts from the top of the unit CHART IV ...

Page 41: ...118 IPI 1 v1 00 August 5 2020 Page 41 CL2118 IPI 1 INSTALLATION 12 in 30 5 cm to 24 61 cm VENT TERMINATION RESTRICTIONS Fig 11 VENT TERMINATION RESTRICTIONS REFER TO Table 1 Table 1 VENT TERMINATION CLEARANCES ...

Page 42: ... a ceiling firestop is required at the second floor and any subsequent floors Fig 27 The opening should be framed to 10 254 mm x 10 254 mm inside dimensions in the same manner as shown in Fig 25 Any occupied areas above the first floor including closets and storage spaces which the vertical vent passes through must be enclosed The enclosure may be framed and sheet rocked with standard building mat...

Page 43: ... is necessary it can be adjusted as follows 1 Turn off the appliance and allow it to cool down completely 2 Remove the face and safety screen and set them aside 3 Lift the restrictor tab off of the restrictor index plate Fig 28 4 Adjust the restrictor index plate to one of the slots to obtain desired flame and reset the restrictor tab into the restrictor index plate slot Fig 29 5 Reinstall the fac...

Page 44: ...closed slightly until the correct flames are achieved Slide the air shutter to the right to reduce the amount of air 5 Flames that are very orange with tall dark stringy tips are not getting enough air Therefore the air shutter should be opened slightly until the correct flames are achieved Slide the air shutter to the left to increase the amount of air 6 Tighten air shutter lock screw BURNER FLAM...

Page 45: ...f the home THE STRUCTURAL INTEGRITY OF THE MANUFACTURED HOME S FLOOR WALL AND CEILING ROOF MUST BE MAINTAINED Fig 31 ELECTRICAL REQUIREMENTS ELECTRICAL GROUNDING INSTRUCTIONS THIS APPLIANCE IS EQUIPPED WITH A JUNCTION BOX AND GROUND SCREW FOR YOUR PROTECTION AGAINST SHOCK HAZARD ENSURE PROPER GROUNDED WIRING IS SUPPLIED AND CONNECTED TO THIS UNIT ELECTRICAL GROUNDING INSTRUCTIONS LABEL ALL WIRES P...

Page 46: ...180 CL2118 IPI 1 v1 00 August 5 2020 Page 46 CL2118 IPI 1 600 584 045 PROFLAME TRANSMITTER CONFIGURATION FOR CLARITY CL2118 IPI INSTALLATION ...

Page 47: ...Pipe Length Black 46DVA 48B 902B 48 Pipe Length Galvanized 46DVA 48 902 11 14 5 8 Adjustable Pipe Length Black 911B 17 24 Adjustable Pipe Length Black 917B 45 Elbow Black 46DVA E45B 945B 945BG 45 Elbow Galvanized 46DVA E45 945 945G 90 Elbow Galvanized 46DVA E90 990 990G 90 Elbow Black 46DVA E90B 990B 990BG Vertical High Wind Termination Cap must be used for all vertical terminations 46 DVA VCH 991...

Page 48: ...ORM DV ADJUSTABLE PIPE EXTENSION BLACK 94610616A 4 to 16 GALVANIZED PRO FORM DV ADJUSTABLE PIPE EXTENSION 94610616AB 4 to 16 GALVANIZED PRO FORM DV ADJUSTABLE PIPE EXTENSION BLACK DIRECT VENT ELBOWS 94620630 30 DEG GALVANIZED PRO FORM DV ELBOW 94620630B 30 DEG GALVANIZED PRO FORM DV ELBOW BLACK 94620645 45 DEG GALVANIZED PRO FORM DV ELBOW 94620645B 45 DEG GALVANIZED PRO FORM DV ELBOW BLACK 9462066...

Page 49: ...LING FIRESTOP Attic Insulation Shield 94930620A 4 INSIDE 6 5 8 PRO FORM DV ATTIC INSULATION SHIELD Adjustable Cathedral Celing Support Kit 949506KT 4 INSIDE 6 5 8 PRO FORM DV CATHEDRAL CEILING SUPPORT KIT Decorator Collar 94940612 4 INSIDE 6 5 8 PRO FORM DV DECORATOR COLLAR SS Counter Flashing 4 Pc Kit 94820615S 4 INSIDE 6 5 8 PRO FORM DV SS COUNTER FLASHING 4 PC KIT SS Vinyl Siding Standoff 94800...

Page 50: ...DT AJ12 DIRECT TEMP 12 ADJ PIPE LENGTH 1604082B 4DT AJ12B DIRECT TEMP 12 ADJ PIPE LENGTH BLACK 1604084 4DT TL14 DIRECT TEMP TELESCOPIC LENGTH 14 22 1604084B 4DT TL14B DIRECT TEMP TELESCOPIC LEN BLACK 14 22 1604086 4DT TL38 DIRECT TEMP TELESCOPIC LENGTH 38 70 1604086B 4DT TL38B DIRECT TEMP TELESCOPIC LEN 38 70 BLACK 4 x 6 5 8 FITTINGS 1604215 4DT EL45 45 DEGREE ELBOW 1604215B 4DT EL45B 45 DEGREE EL...

Page 51: ... Elbow 4D7B 7 Length Black 4D90LB 90 Elbow Black 4D12 12 Length 4DWT Wall Thimble 4D12B 12 Length Black 4DVC Vertical Cap 4D2 24 Length 502672 Horizontal Cap Square 4DHCS 4D2B 24 Length Black 4D36S Siding Shield for 4DHCS 4DHVS 4D3 36 Length 4DHWS Wind Screen 4D3B 36 Length Black 4DWS Wall Strap 4D4 48 Length 4DFSP Firestop Support Plate 4D4B 48 Length Black 4DF Flashing 0 12 6 12 Pitch 4D7A 7 Adj...

Page 52: ...ection VDV 04MT 4 Medium Telescoping Section VDV 04ST 4 Small Telescoping Section VDV AIS04 4 Attic Insulation Shield VDV CAC04 4 Co Linear Appliance Adapter VDV CRS04 4 Round Support Box VDV CSS04 4 Square Support Box VDV EL0445 4 x 45 Deg Direct Vent Elbow VDV EL0445 6 4 x 45 Deg DV Elbow 6 Pack VDV EL0490 4 x 90 Deg Direct Vent Elbow VDV EL0490 6 4 x 90 Deg DV Elbow 6 Pack VDV F0406 4 0 12 6 12...

Page 53: ...DL3B 48 Length Galvalume TC 4DL4 48 Length Black TC 4DL4B 4 x 6 5 8 ELBOWS Elbow 45º Galvalume TE 4DE45 Elbow 45º Black TE 4DE45B Elbow 90º Galvalume TE 4DE90 Elbow 90º Black TE 4DE90B Slip Elbow 90º TE 4DE90S Slip Elbow 90º Black TE 4DE90SB 4 x 6 5 8 SUPPORTS FIRESTOPS Square Support Radiation Shield TM 4SS Round Support Radiation Shield TM 4RDS Ceiling Support Firestop TM 4CS Insulated Wall Thim...

Page 54: ...g 32 6 Undo the inlet gas lines from valve 7 Disconnect all electrical connections to valve including ground wire 8 Remove the screws securing the burner and valve assembly to the to the firebox Pull the burner and valve assembly up out of the firebox Fig 33 9 Undo the gas lines and pilot line from the valve 10 Remove the four screws holding the valve and valve bracket to the firebox bottom and re...

Page 55: ...E 11 600 584 665 PF2 IFC BOARD 3 130 0501 L GLASS CERAM MIRROR LEFT 12 600 885 009 PF2 VALVE W STEPPER MOTOR 4 620 5101 CERAMIC PANEL REAR CLARITY 13 140 5006 BATTERY HOLDER 4 AA 6V 5 130 0501 R GLASS CERAM MIRROR RIGHT 14 640 5101 BURNER ASSEMBLY 6 130 0601 BLACK FLOOR GLASS 15 S Z5277 IPI OPTIONAL FAN KIT COMPLETE 7 Z5104 FLOOR PLATE RIVET ASM 16 600 574 045 PF2 WALL MOUNT TRANSMITTER 8 S Z5175 ...

Page 56: ...em is reset 2 Low battery condition 4V the LED indicator will blink one 1 time in intervals 3 Parasitic Pilot Flame the LED indicator will blink two 2 times in intervals 4 System Lock out the LED indicator will blink three 3 times in intervals Additional Ignition Information 1 The Proflame2 IFC will try two 2 times for ignition 2 Each try for ignition will last approximately 60 seconds 3 The wait ...

Page 57: ...ngs and connections to the board Check the pilot burner for obstruction Check the wirings and connections between the pilot assembly and the board Check the correct gas type settings on the valve and pilot burner assembly orifice Pilot will not remain lit Problem with Flame Sensor circuit Check for proper connection of the Flame Sensor to the IFC board Check pilot for full flame impingement around...

Page 58: ...nt on thermopile Flame lifting Leak in vent pipe Check for leaks in vent connections Improper vent configuration Check vent configuration with manual Terminal may be re circulating flue gases Check to see if terminal is on correctly May need to install high wind termination cap Contact dealer Blue Flames The heater has just been started Normal during start up flame will yellow as the fireplace hea...

Page 59: ...Warranty Period Components Covered Parts Labor Gas 1 Year X All parts materials and surface finishes flaking and peeling Except as covered by Conditions Exclusion and Limitations listed 2 Years Parts 1 Year Labor X Igniters thermocouple thermopile molded refractory panels log sets interior glass panels fan assembly ignition components gas valve burner components thermostat 5 Years 2 Years X Firebo...

Page 60: ...nd exclusions apply to this warranty Limited One 1 Year Warranty Under this warranty Blaze King covers all exterior surface finishes against defects in materials and workmanship for part repair or replacement and limited labor for the first 1 year to the original purchaser Please see the exclusions and limitations section below as certain restrictions and exclusions apply to this warranty How the ...

Page 61: ...this stove If unsure as to the extent of this Limited Warranty contact your authorized Blaze King dealer before installation 9 Blaze King will not be responsible for inadequate performance caused by environmental conditions 10 The Limited Warranty does not cover installation and operational related problems such as use of downdrafts or spillage caused by environmental conditions Environmental cond...

Page 62: ...le Blaze King will not be liable for travel costs for service work In the event of in home repair work the customer will pay any in home travel fees or service charges required by the Authorized Dealer 27 At no time will Blaze King be liable for any consequential damages which exceed the purchase price of the unit Blaze King has no obligation to enhance or modify any stove once manufactured exampl...

Reviews: