Page 1: ...Centrifugal fan USER S MANUAL EN Centro EC ...

Page 2: ...ro EC unit and all its modifications Technical and maintenance staff must have theoretical and practical training in the field of ventilation systems and should be able to work in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of the country The information in this user s manual is correct at the time of the document s preparation The...

Page 3: ...iving operator UNIT INSTALLATION AND OPERATION SAFETY PRECAUTIONS Disconnect the unit from power mains prior to any installation operations Unpack the unit with care The unit must be grounded While installing the unit follow the safety regulations specific to the use of electric tools Do not change the power cable length at your own discretion Do not bend the power cable Avoid damaging the power c...

Page 4: ...disconnect it from power supply and contact the Seller Do not open the unit during operation Do not direct the air flow produced by the unit towards open flame or ignition sources Do not block the air duct when the unit is switched on In case of continuous operation of the unit periodically check the security of mounting Do not sit on the unit and avoid placing foreign objects on it Use the unit o...

Page 5: ... bracket 2 pcs User s manual 1 pc Packing box 1 pc Centro EC 100 X Additional options FR1 integrated smooth speed controller G1 speed controller with an electronic thermostat and an external temperature sensor fixed on a 4 meter cable Power cable with mains plug Temperature based operation logic GT1 speed controller with an electronic thermostat and an external temperature sensor fixed on a 4 mete...

Page 6: ...heater must be grounded The unit design is constantly being improved thus some models may be slightly different from those described in this manual Parameter Centro EC 100 Centro EC 125 Centro EC 150 Centro EC 200 Centro EC 250 Centro EC 315 Unit voltage V 50 60 Hz 1 230 1 230 1 230 1 230 1 230 1 230 Power W 82 84 82 84 165 165 Current A 0 62 0 64 0 63 0 64 1 10 1 15 Maximum air flow m3 h 340 420 ...

Page 7: ...is case fan speed switching operations are rare The TSI lights up and the fan switches to the maximum speed as the room air temperature exceeds the set point As the air temperature drops 2 C below the set point or if the initial temperature is below the set point the TSI goes out and the fan operates with the set speed Centro EC GT1 GTI1 The speed switching operations are more frequent as compared...

Page 8: ...ews 5 Connect the air ducts of the corresponding diameter to the fan MOUNTING AND SET UP The fan is suitable both for horizontal or vertical mounting on the floor on the wall or on the ceiling Air motion in the system must be in compliance with the direction of the arrow on the fan casing Install a hood on the intake spigot side in case of vertical fan installation When installing the fan horizont...

Page 9: ... maximum conductor temperature depending on the wire type insulation length and installation method The external power input must be equipped with an automatic circuit breaker built into the stationary wiring to open the electric circuit in case of overload or short circuit The circuit breaker installation place must provide quick access for emergency shutdown of the unit The trip current of the a...

Page 10: ...be transported only in the working position Avoid sharp blows scratches or rough handling during loading and unloading Prior to the initial power up after transportation at low temperatures allow the unit to warm up at operating temperature for at least 3 4 hours DISCONNECT THE UNIT FROM POWER SUPPLY BEFORE ANY MAINTENANCE OPERATIONS TECHNICAL MAINTENANCE Clean the product surfaces regularly once ...

Page 11: ...the Seller for warranty service The manufacturer s warranty does not apply to the following cases User s failure to submit the unit with the entire delivery package as stated in the user s manual including submission with missing component parts previously dismounted by the user Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user s manual...

Page 12: ...rtify acceptance of the complete unit delivery with the user s manual The warranty terms are acknowledged and accepted Customer s Signature INSTALLATION CERTIFICATE The Centro EC________ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s Full Name Installation Date Signature The unit has ...

Page 13: ...www blaubergventilatoren de Centro EC 13 ...

Page 14: ...Centro EC 14 www blaubergventilatoren de ...

Page 15: ...www blaubergventilatoren de Centro EC 15 ...

Page 16: ...www blaubergventilatoren de B02 1EN 02 ...

Reviews: