USER’S MANUAL

EN

Box

Summary of Contents for Box Series

Page 1: ...Inline rectangular fans USER S MANUAL EN Box ...

Page 2: ...me of the document s preparation The Company reserves the right to modify the technical characteristics design or configuration of its products at any time in order to incorporate the latest technological developments No part of this publication may be reproduced stored in a retrieval system or transmitted in any form or by any means in any information search system or translated into any language...

Page 3: ...ice life of the unit While transferring the unit control the user s manual must be turned over to the receiving operator UNIT INSTALLATION AND OPERATION SAFETY PRECAUTIONS Disconnect the unit from power mains prior to any installation operations Unpack the unit with care The unit must be grounded While installing the unit follow the safety regulations specific to the use of electric tools Do not c...

Page 4: ...nit from power mains prior to any technical maintenance Do not store any explosive or highly flammable substances in close proximity to the unit When the unit generates unusual sounds odour or emits smoke disconnect it from power supply and contact the Seller Do not open the unit during operation Do not direct the air flow produced by the unit towards open flame or ignition sources Do not block th...

Page 5: ...LD NOT BE OPERATED BY CHILDREN OR PERSONS WITH REDUCED PHYSICAL MENTAL OR SENSORY CAPACITIES OR THOSE WITHOUT THE APPROPRIATE TRAINING THE UNIT MUST BE INSTALLED AND CONNECTED ONLY BY PROPERLY QUALIFIED PERSONNEL AFTER THE APPROPRIATE BRIEFING THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT UNAUTHORIZED ACCESS BY UNATTENDED CHILDREN Name Quantity Fan 1 pc User s manual 1 pc Packing box 1 pc ...

Page 6: ...age V 50 Hz 3 400 1 230 3 400 1 230 3 400 Power W 274 710 855 283 303 Current A 0 67 3 10 1 70 1 59 0 8 Max air capacity m3 h 1490 2350 2350 1550 1620 RPM min 1 930 1230 1300 890 910 Noise level at 3 m dBA 45 38 57 47 56 47 47 39 51 41 Transported air temperature C 20 60 25 70 20 50 20 70 20 60 Protection rating IPX4 IPX4 IPX4 IPX4 IPX4 Box F Box FI 60x30 4E Box F Box FI 60x30 4D Box F Box FI 60x3...

Page 7: ...0 6D Box F Box FI 80x50 8D Voltage V 50 Hz 3 400 3 400 3 400 3 400 Power W 1150 5850 2790 1377 Current A 2 3 9 35 5 18 3 40 Max air capacity m3 h 4050 8120 7610 5620 RPM min 1 890 1140 830 710 Noise level at 3 m dBA 58 49 67 61 59 53 58 49 Transported air temperature C 20 70 25 40 20 50 20 40 Protection rating IPX4 IPX4 IPX4 IPX4 Box F Box FI 60x35 4D Box F Box FI 60x35 6E Box F Box FI 60x35 6D Bo...

Page 8: ...680 35 Box F 60x30 4D 600 620 640 300 320 340 375 680 35 Box F 60x30 6E 600 620 640 300 320 340 375 680 35 Box F 60x30 6D 600 620 640 300 320 340 375 680 35 Box F 60x35 4E 600 620 640 350 370 390 425 735 49 5 Box F 60x35 4D 600 620 640 350 370 390 425 735 49 5 Box F 60x35 6E 600 620 640 350 370 390 425 735 49 5 Box F 60x35 6D 600 620 640 350 370 390 425 735 49 5 Box F 70x40 4D 700 720 740 400 420 ...

Page 9: ... 600 620 640 670 300 320 340 480 680 56 Box FI 60x30 4D 600 620 640 670 300 320 340 480 680 56 Box FI 60x30 6E 600 620 640 670 300 320 340 480 680 56 Box FI 60x30 6D 600 620 640 670 300 320 340 480 680 56 Box FI 60x35 4E 600 620 640 670 350 370 390 530 735 72 Box FI 60x35 4D 600 620 640 670 350 370 390 530 735 72 Box FI 60x35 6E 600 620 640 670 350 370 390 530 735 72 Box FI 60x35 6D 600 620 640 67...

Page 10: ...00 2500 2040 2040 Noise level at 3 m dBA 58 60 63 65 69 69 Transported air temperature C 25 60 25 50 25 40 25 40 25 40 25 40 Protection rating IPX4 IPX4 IPX4 IPX4 IPX4 IPX4 Box EC Type Dimensions mm Weight kg B B1 B2 H H1 H2 H3 L Box EC 60x30 600 620 640 300 320 340 430 680 35 0 Box EC 60x35 600 620 640 350 370 390 480 735 49 5 Box EC 70x40 700 720 740 400 420 440 540 780 60 0 Box EC 80x50 800 820...

Page 11: ...75 810 1000 1045 800 128 0 Box I EC 100x50 1000 500 1020 520 1175 810 1000 1145 800 129 0 Box I EC 60x30 Box I EC 60x35 Box I EC 70x40 Box I EC 80x50 Box I EC 90x50 Box I EC 100x50 Voltage V 50 60 Hz 1 200 277 3 380 480 3 380 480 3 380 480 3 380 480 3 380 480 Power kW 0 48 0 99 1 70 2 95 2 98 2 98 Current A 3 10 1 70 2 60 4 60 4 60 4 60 Max air capacity m3 h 3350 4550 6300 8900 10850 10850 RPM min...

Page 12: ... 60 Power W 138 200 305 380 140 165 136 165 Current A 0 60 0 88 1 32 1 65 0 57 0 53 0 34 0 53 Max air capacity m3 h 930 1070 1720 1850 1700 1620 1380 1620 RPM min 1 2600 2850 2550 2830 1390 1530 1360 1600 Noise level at 3 m dBA 59 51 71 63 61 53 78 67 53 45 55 46 53 45 55 46 Transported air temperature C 25 45 25 45 25 45 25 50 25 65 25 55 Protection rating IPX4 IPX4 IPX4 IPX4 Box Box I 60x30 4E B...

Page 13: ...70 390 390 735 36 38 Type Dimensions mm Weight kg B B1 B2 B3 H H1 H2 H3 L Box I 40x20 2E 400 420 440 500 200 220 240 360 500 24 5 Box I 50x25 2E 500 520 540 600 250 270 290 410 640 27 6 Box I 50x30 4E 500 520 540 600 300 320 340 460 680 37 2 Box I 50x30 4D 500 520 540 600 300 320 340 460 680 37 2 Box I 60x30 4E 600 620 640 700 300 320 340 460 680 43 5 Box I 60x30 4D 600 620 640 700 300 320 340 460...

Page 14: ...rection in the system must match the direction of the arrow on the fan casing Remember to mount the fan on the additional internal brackets to avoid load transfer to the flexible connectors The most suitable mounting option is fixation of the fan to the ceiling with anchor bolts or suspension of the fan to the perforated metal plates Apply self adhesive sealer on the fan end surfaces prior to moun...

Page 15: ...tch the rated current consumption of the fan The recommended rated current of the automatic circuit breaker and wire cross section of various fan types are stated in the table stated on page 16 The stated wire cross sections are for reference only The actually required wire cross section depends on the cable type insulation length and its layout way open channel or wall mounting Connect EC fans to...

Page 16: ...0 75 Box 100x50 4D 8 5x1 0 Box EC Box I EC 60x30 4 3x0 75 Box EC Box I EC 60x35 2 5x0 75 Box EC Box I EC 70x40 4 5x0 5 Box EC Box I EC 80x50 6 5x1 0 Box EC Box I EC 90x50 6 5x1 0 Box EC Box I EC 100x50 6 5x1 0 Box F Box FI 40x20 4E 2 3x0 75 Box F Box FI 40x20 4D 1 5x0 75 Box F Box FI 50x25 4E 4 3x0 75 Box F Box FI 50x25 4D 1 6 5x0 75 Box F Box FI 50x30 4E 4 3x0 75 Box F Box FI 50x30 4D 2 5x0 75 Bo...

Page 17: ... 60 Hz L2 L1 X1 2 7 1 3 L3 L3 5 4 6 V1 U1 W1 W2 PE U2 V2 L1 L2 L3 8 9 TW2 TW1 TW1 TW2 TW1 TW2 PE PE Wiring diagram of the fan Box Box I 50x30 4D second option Box Box I 60x30 4D with a three phase motor to the alternating current power supply Wiring diagram of the fan Box Box I 60x35 4D with a three phase motor to alternating current power supply L N X1 1 2 3 N L QF PE 230 V 50 60 Hz 4 PE L2 L1 QF...

Page 18: ...V 50 Hz L2 L1 X1 4 9 3 5 L3 L3 7 6 8 U1 W2 W1 PE U2 V2 L1 L2 L3 V1 РЕ WIRING DIAGRAM OF THE FANS BOX F BOX FI WITH A THREE PHASE MOTOR TO THE ALTERNATING CURRENT POWER SUPPLY N L QF PE 230 V 50 Hz L N X1 3 6 2 5 4 1 TK1 TK2 TK2 TK1 РЕ 1 2 TW1 TW2 TW1 TW2 L2 L1 QF PE 400 V 50 Hz L2 L1 X1 4 9 3 5 L3 L3 7 6 8 U1 W2 W1 PE U2 V2 L1 L2 L3 V1 РЕ where X1 is a terminal block QF is an automatic circuit bre...

Page 19: ...nput control input GND Ground interface RS485 for ebmBUS RS B interface RS485 for ebmBUS RS A interface RS485 for ebmBUS RS B WIRING DIAGRAM FOR THE FANS BOX EC 60X35 BOX I EC 60X35 Contact Connection Colour Black Blue Green Yellow White 1 White 2 Red Yellow Blue Purpose Function Power supply 50 60 Hz phase Power supply 50 60 Hz zero Ground cable Fault relay normally closed contact Fault relay COM...

Page 20: ...ace RS485 for ebmBUS RS A interface RS485 for ebmBUS RS B interface RS485 for ebmBUS RS A WIRING DIAGRAM FOR THE FANS BOX EC 80X50 BOX EC 90X50 BOX EC 100X50 BOX I EC 80X50 BOX I EC 90X50 BOX I EC 100X50 Terminal Connection Purpose Function Net L3 Net L2 Net L1 Ground cable Alarm relay normally closed contact Alarm relay COMMON 2A 250V Ac1 Alarm relay normally open contact Terminal Connection Purp...

Page 21: ...M1 L2 L3 QF 400 V 50 60 Hz L1 L2 L3 N PE PE X1 RECOMMENDED WIRING DIAGRAM FOR CONNECTION OF THE THREE PHASE MOTOR WITH OVERHEATING PROTECTION N 2 3 N PE TW 1 4 5 6 TW 2 230 V 50 60 Hz S1 ON S2 OFF РЕ L1 TW1 TW2 S1 ON S2 OFF KM1 L2 L3 QF 400 V 50 60 Hz L1 L2 L3 N PE PE X1 where X1 is a terminal block QF is an automatic circuit breaker Km1 is a magnetic starter S1 S2 are control buttons QF KM1 S1 S2...

Page 22: ...www blaubergventilatoren de Box 22 BOX BOX I BOX F BOX FI 40X20 50X25 50X30 60X30 60X35 1 3 2 4 1 3 2 4 BOX F BOX FI 70X40 80X50 90X50 100X50 BOX EC 60X30 BOX I EC 60X30 BOX 100X50 1 3 2 4 1 3 2 4 ...

Page 23: ... Maintenance means regular cleaning of the fan surfaces from dust and dirt Use a soft brush or compressed air to remove dust from metal surfaces of the fan use a vacuum cleaner to remove dust from the sound insulating surface The impeller blades require thorough cleaning once in 6 months Detach air ducts from the fan before starting maintenance works Clean the fan impeller blades with water and mi...

Page 24: ...www blaubergventilatoren de Box 24 1 3 4 5 6 2 ...

Page 25: ...nloading Prior to the initial power up after transportation at low temperatures allow the unit to warm up at operating temperature for at least 3 4 hours TROUBLESHOOTING TROUBLE POSSIBLE REASONS TROUBLESHOOTING The fan does not get started No power supply Check the electric connections and the operation status of the circuit breaker Motor jam Turn the fan off Troubleshoot clogging of the impeller ...

Page 26: ... Seller for warranty service The manufacturer s warranty does not apply to the following cases User s failure to submit the unit with the entire delivery package as stated in the user s manual including submission with missing component parts previously dismounted by the user Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user s manual Us...

Page 27: ...TION CERTIFICATE The Box_____________ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s Full Name Installation Date Signature The unit has been installed in accordance with the provisions of all the applicable local and national construction electrical and technical codes and standards T...

Page 28: ...www blaubergventilatoren de B07EN 03 ...