7
www.blaubergventilatoren.de
Clean Box
DESIGN AND OPERATING PRINCIPLE
The unit is a box with filters of different filter class installed in it.
Each unit involves installation of up to three filters with different supply air filter classes (from coarse to more fine cleaning).
The air flow direction is indicated by the arrow on the fan casing.
G4
ES
G4
Car
bon
F8(H13)
Air intake
Air exhaust
Air intake
Air exhaust
INSTALLATION AND SET-UP
The unit is suspended to the mounting surface through the threaded rod fixed inside the expansion anchor.
While installing the unit, ensure convenient access for subsequent maintenance and repair.
Fasteners for ceiling mounting are not included into delivery set and should be ordered separately.
While choosing fasteners, consider the material of the mounting surface as well as the weigh of the unit, refer to the Technical data
section.
Fasteners for unit mounting should be selected by the service technician.
min А mm
Nut
Washer
Vibration absorbing
rubber
Washer
Nut and lock nut
min 10 mm
Service side
To get the best performance of the ventilation system and to minimize turbulence-induced air pressure losses, connect the straight air
duct section to the spigots on both sides of the unit while installing.
Minimum straight air duct length:
equal to 1 air duct diameter on intake side
equal to 3 air duct diameters on outlet side
READ THE USER'S MANUAL BEFORE INSTALLING THE UNIT.
Clean Box ... G4-F8(H13)-C
Clean Box ... ES