BLAUBERG Ventilatoren BOX 100 User Manual Download Page 7

7

www.blaubergventilatoren.de

Clean Box

DESIGN AND OPERATING PRINCIPLE

The unit is a box with filters of different filter class installed in it. 
Each unit involves installation of up to three filters with different supply air filter classes (from coarse to more fine cleaning). 
The air flow direction is indicated by the arrow on the fan casing.

G4

ES

G4

Car

bon 

F8(H13)

Air intake

Air exhaust

Air intake

Air exhaust

INSTALLATION AND SET-UP

The unit is suspended to the mounting surface through the threaded rod fixed inside the expansion anchor.
While installing the unit, ensure convenient access for subsequent maintenance and repair. 
Fasteners for ceiling mounting are not included into delivery set and should be ordered separately. 
While choosing fasteners, consider the material of the mounting surface as well as the weigh of the unit, refer to the Technical data 
section.
Fasteners for unit mounting should be selected by the service technician.

min А mm

Nut
Washer
Vibration absorbing 
rubber
Washer
Nut and lock nut

min 10 mm

Service side

To get the best performance of the ventilation system and to minimize turbulence-induced air pressure losses, connect the straight air 
duct section to the spigots on both sides of the unit while installing.
Minimum straight air duct length: 
equal to 1 air duct diameter on intake side 
equal to 3 air duct diameters on outlet side

READ THE USER'S MANUAL BEFORE INSTALLING THE UNIT.

Clean Box ... G4-F8(H13)-C

Clean Box ... ES

Summary of Contents for BOX 100

Page 1: ...USER S MANUAL Clean Box 100 Clean Box 125 Clean Box 150 Clean Box 200 FILTER BOX WITH PANEL FILTERS FOR ROUND AIR DUCTS EN...

Page 2: ...ata 5 Design and operating principle 7 Installation and set up 7 Connection to power mains 8 Technical maintenance 9 Storage and transportation regulations 9 Manufacturer s warranty 10 Certificate of...

Page 3: ...ct the electric parts of the unit against ingress of water Do not allow children to operate the unit Disconnect the unit from power mains prior to any technical maintenance Do not store any explosive...

Page 4: ...ulation ventilation systems for the purification of air in private homes offices hotels caf s conference halls and other utility and public spaces The unit is intended for suspended mounting Transport...

Page 5: ...400 47 Clean Box 100 G4 H13 G4 H13 220 400 47 220 400 47 Clean Box 100 G4 H13 C G4 H13 Carbon 220 400 47 220 400 47 220 400 47 Clean Box 100 ES G4 ES 220 400 47 Clean Box 125 G4 F8 G4 F8 220 400 47 2...

Page 6: ...125 G4 H13 125 413 5 249 415 513 5 508 358 5 458 Clean Box 125 G4 H13 C 125 413 5 249 415 513 5 508 358 5 458 Clean Box 125 ES 125 513 5 250 458 613 5 551 456 502 Clean Box 150 G4 F8 150 413 5 299 440...

Page 7: ...epair Fasteners for ceiling mounting are not included into delivery set and should be ordered separately While choosing fasteners consider the material of the mounting surface as well as the weigh of...

Page 8: ...URER S LABEL ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED AND WILL VOID THE WARRANTY The unit is rated for connection to single phase AC 230 V 50 Hz power mains The connection must be mad...

Page 9: ...er up after transportation at low temperatures allow the unit to warm up at operating temperature for at least 3 4 hours DISCONNECT THE UNIT FROM POWER SUPPLY BEFORE ANY MAINTENANCE OPERATIONS TECHNIC...

Page 10: ...y does not apply to the following cases User s failure to submit the unit with the entire delivery package as stated in the user s manual including submission with missing component parts previously d...

Page 11: ...complete unit delivery with the user s manual The warranty terms are acknowledged and accepted Customer s Signature The Clean Box _______ unit is installed pursuant to the requirements stated in the...

Page 12: ...www blaubergventilatoren de B185EN 05...

Reviews: