![BLAUBERG Ventilatoren Altero 150 T User Manual Download Page 7](http://html1.mh-extra.com/html/blauberg-ventilatoren/altero-150-t/altero-150-t_user-manual_2770014007.webp)
POWER OFF THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT.
THE UNIT MUST BE CONNECTED TO POWER SUPPLY BY A QUALIFIED ELECTRICIAN.
THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE
MANUFACTURER’S LABEL.
• The unit is rated for connection to 1~120 V/60 Hz power mains, depending on the model, according to the wiring diagram.
• The unit must be connected to power mains using insulated electric conductors (cables, wires). The actual wire cross section
selection must be based on the maximum load current, maximum conductor temperature depending on the wire type, insulation,
length and installation method.
• The external power input must be equipped with an automatic circuit breaker built into the stationary wiring to open the electric
circuit in case of overload or short-circuit. The circuit breaker installation place must provide quick access for emergency shutdown
of the unit. The trip current of the automatic circuit breaker must exceed the maximum current consumption of the unit (refer to
the technical data table). The recommended trip current of the circuit breaker is the next current in the standard trip current row
following the maximum current of the connected unit. The automatic circuit breaker is not included in the delivery set.
Access to the control unit
To access the control unit, undo the screws securing the
removable electric mounting plate and pull it towards you until
it stops.
Pull the power cable through the glands on the side of the
control unit and make the electrical connections as shown in
the wiring diagram.
L N PE L N PE
Wiring diagram example
X1
QF*
PE
N
L
PE
N
L
L
N PE
PE
N
L
PE
N
L
24 V
E X H
S U P
~24 V
S1*
S2*
~120 V
~120 V
EXH, SUP, 24V
Connectors on the board in the control unit
X1
Terminal block in the control unit
S1*, S2*
External sensors
QF*
Circuit breaker
*Additionally connected devices are purchased separately.
CONNECTION TO POWER MAINS
www.blaubergventilatoren.de
altero 150 T
7