6
POWER AND GROUNDING
WARNING:
To avoid injury to persons or loss of life, ground each cabinet individually to the dedicated branch circuit ground.
Connecting Main Protective Grounding Stud to the Dedicated Branch Circuit Ground
Connect the dedicated branch circuit ground connector to the main protective grounding stud located inside the
cabinet on the back of the rear section and inside the cabinet on the side using a listed ring or closed-loop terminal.
Connecting Main Protective Grounding Stud to the Protective Bonding Conductors
Connect the middle wall mount frame on the cabinet to the main protective grounding stud located inside the
cabinet on the back of the rear section using a listed ring or closed-loop terminal.
Parts Not Bonded to Protective Earthing Terminal
The rails are not effectively bonded to the protective earthing terminal. If these parts need to be bonded to the
protective earthing terminal, do so in accordance with Article 250 of the National Electrical Code.