background image

PSE518SA 

Satellite  is  a  power  distribution  and  control  unit  that  enables  power 

management of 8 devices through an RS-232 or RS-485 serial connection.

The number of controlled power outlets can be extended up to 128 by cascading 
up to 16 Satellite models.

This Power Switch is ideal to control power outlets through the serial connection 
of a PC, a KVM switch or a console server. It can also be connected to a Secure 
Power Switch Master to extend the number of controlled power outlets over IP. 

Before  operating  your  Power  Switch,  please  read  the  safety 
instructions in the User Guide on the provided CD-ROM.

Detailed information can be found in the 

User Guide on the provided CD-ROM

Quick Start Guide

January 2007

PSE518SA

© Copyright 2007

Black Box Corporation 

All rights reserved

Secure Power Switch

Satellite 8 - Port

P

o

w

e

S

w

it

c

h

FREE technical support

SUPPORT 

To read out the status of power outlets from your computer, enter the command 
as explained below:

Syntax of the command:

Rxy <ENTER>

Parameter     Value       Function

X                1 to 16     means the address of the Satellite (see table 

§

1)

Y                1 to 8       indicates the number of the power outlet you want to control

The Secure Power Switch then sends the status of the specified power outlet using 
following syntax:
Pxy=z<CR><LF>
z = 0 if the power outlet is off
z = 1 if the power outlet is on
<CR> = Carriage Return
<LF>  = Line Feed

Examples

:

Read out the status of the power outlet 5 of the Satellite with address 1:
R15   <ENTER> 
Read out the status of the power outlet 6 of the Satellite with address 2:
R26  <ENTER> 

Remark

The Power Switch accepts lower case and upper case commands.

Pinout of the RJ11 6/6 x-Bus connector

RJ11 6/6 FRONT VIEW

1 2 3 4 5 6

The power supply delivers a voltage of 7V +-10% for a load of 100mA. The output 
is overload protected and protected against polarity inversion. The xBus connectors 
of  both  Secure  Power  Switch  Master  and  Satellite  have  the  same  features  and 
pinout.
The symmetrical pinout of power output (+Vout) and GND prevents the risk of short 
circuits if the RJ11 connector is inverted.

Pin

Signal

1

+Vout (+7V / 100mA)

2

GND

3

RS485 – B

4

RS485 – A

5

GND

6

+Vout (+7V / 100mA)