Chapter 5: Maintenance
M6 hex bolts
(two per side)
Fan
Power/control
connectors
Figure 5-6. 24" cabinet.
Remove the four hex-bolts holding the inlet ring then remove the four hex-bolts holding the fan mounting bracket. Remove the
fan assembly together with the inlet ring from the cabinet. Remove the mounting bracket from the old fan and install it on the
new fan. Bolt the new fan assembly (together with the inlet ring) into the cabinet and plug the power and control cables into the
connectors.
5.3.2.3 Condensate Pump Replacement
The condensate pump is located behind the lower cabinet fan assembly (see the figures in Sections 2.7.1.1 and 2.7.1.2). To access
the pump, the lower fan must be removed as described in Section 5.3.2.2.
Cable loop
Retaining
clip
Pump
Wire tie
Discharge
line