CB-100-1
49
Type
Rated in-
put current
Minimum .. maximum cable diameters and tightening
torques (in Nm)
Fuses
Power connections
Earth connections
Rated fuse
current (amp.)
Amp.
Nm
Nm
Stand-
ard
UL,
cUL
Type
FDU+6
7.6
0.05 .. 6 mm
2
0.56 ..
0.8
M4
ring cable lug
1.8
10
10
Class J
FDU+12
10.6
16
20
Class J
FEU+16
14.5
20
25
Class J
FEU+24
20.4
25
30
Class J
FGU+32
28.5
1 .. 10 mm
2
(16 mm² with cable
connector)
1.35
M4
ring cable lug
1.8
32
40
Class J
FGU+38
33.5
40
50
Class J
FHU+45
40
1.3 .. 25 mm
2
2.0
M5
ring cable lug
3.6
63
60
Class J
FHU+60
54.7
80
80
Class J
FHU+73
66.2
100
100
Class J
FJU+87
78.8
Pin M8 for cable lugs
or wire end sleeves
up to a length of
26.5 mm
(min. 25 mm
2
)
20
M8
ring cable lug
20
125
125
A50QS-125-4
FJU+105
95.8
160
150
A50QS-150-4
FJU+145
130
200
200
A50QS-200-4
FKU+180
160
M8 pin for cable lugs
or wire end sleeves
up to a length of
32 mm
(min. 25 mm
2
)
20
M8
ring cable lug
20
250
250
A50QS-250-4
FKU+205
198
315
300
A50QS-300-4
FKU+260
236
400
350
A50QS-350-4
Tab. 3: Cable diameters, tightening torques and fuses