DB-300-9
6
3
Application ranges
Type
Fluid group ac-
cording to
2014/68/EU
(PED)
Safety group ac-
cording to EN 378
PS
Maximum
permitted
pressure
TS
Maximum and
minimum permit-
ted temperature
F062H(P) .. F3102N(P), F182 .. F312,
F302G .. F1602G, F212N3,
FS33 .. FS268, FS36(P) .. FS3102(P),
1 + 2
A1, A2, A2L, A3
33 bar
120°C / -10°C
FS4002(P) .. FS5502(P)
1 + 2
A1, A2, A2L, A3
28 bar
120°C / -10°C
F202HA .. F3102NA
1 + 2
A1, A2, A2L, A3,
B2L
28 bar
120°C / -10°C
F302K .. F1602K, FS302K .. FS1602K
1 + 2
A1, A2, A2L, A3
45 bar
(33 bar)
120°C / -10°C
(-10°C / -20°C)
OA1954 .. OA25112,
OAF6288 .. OAF15211,
OAH2888 .. OAH7088
1 + 2
A1, A2, A2L, A3
28 bar
120°C / -10°C
OA1954A .. OA25112A,
OAS322 .. OAS3088, OAC14011A ..
OAC25112A, OAHC65051A .. OAH-
C100051A, OAS322 .. OAS3088
1 + 2
A1, A2, A2L, A3,
B2L
28 bar
120°C / -10°C
OA1954(A) .. OA25112(A),
OAF6288 .. OAF15211,
OAH2888 .. OAH7088,
OAS322 .. OAS3088, OAC14011A ..
OAC25112A, OAHC65051A .. OAH-
C100051A, OAS322 .. OAS3088
Oil according to
ISO 6743-3, DIN 51503-1
28 bar
120°C / -10°C
Tab. 1: Permitted fluids