SB-160-3
7
• Observe the max. refrigerant charge according to the
installation place and the installation zone! See
EN378-1 and local regulations.
• No operation in the vacuum range! Install safety
devices for protection against insufficient and ex-
cessive pressure and make sure that they are de-
signed in accordance with the requirements of the
safety regulations (e.g. EN378-2).
• Avoid air penetration in the system – also during and
after maintenance work!
3.1.2
General operation requirements
Operation of the system and personal protection are
usually subject to national regulations on product
safety, operating reliability and accident prevention. To
this end, separate agreements between the contractor
and the end user must be made. The provision of the
necessary risk assessment for work environment prior
to installation and operation of the system is the re-
sponsibility of the end user. To this end, cooperation
with a notified body is recommended.
• To open the pipelines, use only pipe cutters and no
open flame.
4
Mounting
4.1
Transporting the compressor
Either transport the compressor screwed onto the pallet
or use eyebolts to lift it.
DANGER
Suspended load!
Do not step under the machine!
!
!
NOTICE
In the case of a strong shock or pressure, the FI
housing may break.
Treat the FI housing with care.
Fig. 2: Lifting the CSV. compressor; above: CSV.2; below: CSV.3