12

KB-520-6

Pipelines

Only use tubes and components
which are 
• clean and dry inside (free from

slag, swarf, rust, and phosphate
coatings) and 

• which are delivered with an air tight

seal.

Attention!

Do not overheat the valves!
Plants with longer pipe lines or if
it is soldered without protection
gas: Install cleaning suction side
filter  (mesh size < 25 

μ

m).

Attention!

Compressor damage possible!
Generously sized high qual ity fil -
ter  driers must be used to
 ensure a high  degree of dehy -
dra tion and to main tain the
chem i cal stabil ity of the sys tem
(molecular sieves with specially
adjusted pore sice).

3.6 Start unloading (SU) and

Capacity control (CR)

The upper parts of the valves are
delivered separately packed to avoid
transport damage. These valve parts 
must be fitted in place of the sealing
flanges before the compressor is
evacuated.

Warning!

Compressor is under pressure
by holding charge!
Severe injuries possible.
Release the pressure in the
compressor!
Wear safety goggles!

To avoid mistakes the cylinder head
and the valve flange are marked with
a coding "SU" resp. "CR". A pin in the
flange surface only allows the correct
assembly. See figure 9.

!

!

!

!

!

Tuyauteries

D'une manière générale, on ne doit utiliser
que des tubes et des composants 
• propres et secs à l'intérieur (pas de

calamine, de copeaux métalliques, de
dépôts de rouille et de phosphates) et 

• qui sont livrés hermétiquement clos.

Attention !

Monter un filtre de nettoyage (maille
< 25 µm) à l'aspiration, dans les
installations avec de longues tuyau-
teries ou quand le brasage est réa-
lisé sans gaz inerte.

Attention !

Dégâts sur le compresseur possi-
bles !
Utiliser des filtres déshydrateurs lar-
gement dimensionnés et de qualité
appropriée (tamis moléculaire avec
taille des pores adaptée) afin d'as-
surer le haut niveau de dessiccation
requis et la stabilité chimique du cir-
cuit.

3.6 Démar ra ge à vide (SU) et

Régulation de puis san ce (CR)

Les parties supérieures des vannes sont
livrées séparément afin d'éviter des 
détériorations durant le transport; elles
doivent être montées avant la mise sous
vide. Pour cela, il faut remplacer la bride
d'obturation par la partie supérieure de la
vanne.

Avertissement !

Compresseur est sous pression 
par gaz de protection !
Graves blessures possibles.
Retirer la pression sur le compres-
seur !
Porter des lunettes de protection !

Pour évi ter les confu sions, la tête de
cylin dre et la bride de la vanne sont iden -
ti fiées avec un indi ce "SU" ou plutôt "CR".
Une gou pille de posi tion ne ment logée
dans la bride  assure un assem bla ge cor -
rect. Voir figure 9.

!

!

!

!

!

Rohrleitungen

Grundsätzlich nur Rohr leitun gen und
Anlagen-Komponenten verwenden, die 
• innen sauber und trocken sind (frei

von Zunder, Metall spänen, Rost-
und Phosphat schich ten) und 

• luft dicht verschlossen angeliefert

werden.

Achtung!

Ventile nicht überhitzen!
Bei Anlagen mit längeren Rohr -
leitungen oder wenn ohne
Schutz gas gelötet wird: Saug   -
seitigen Reinigungs filter einbau-
en (Filterfeinheit < 25 

μ

m).

Achtung!

Verdichterschaden möglich!
Im Hinblick auf hohen Trock -
nungs grad und zur chemischen
Stabilisierung des Kreis laufs
müssen reichlich dimensionierte
Filtertrockner geeigneter Qualität
verwendet werden (Molekular-
Siebe mit speziell angepasster
Porengröße).

3.6 Anlaufentlastung (SU) und

Leistungsregelung (CR)

Die Ventil-Oberteile werden zum
Schutz gegen Transportschäden als
Beipack geliefert. Sie müssen vor
dem Evaku ieren montiert werden.
Dazu den Blindflansch gegen das
Oberteil wechseln.

Warnung!

Verdichter steht unter Druck
durch Schutzgas!
Schwere Verletzungen möglich.
Verdichter auf drucklosen
Zustand bringen!
Schutzbrille tragen!

Um Verwechslungen zu vermeiden,
sind Zylinderkopf und Ventilflansch
gekenzeichnet "SU" bzw. "CR". Ein
Pass-Stift in der Flansch fläche erlaubt
nur die richtige Positio nie rung. Siehe
hierzu Abbildung 9.

!

!

!

!

!

Summary of Contents for 2N.2 Series

Page 1: ...cording to the existing instruction and as a whole agree with the corresponding provisions of legislation standards to apply refer to Manufacturers Declara tion Authorized staff All work on compressor...

Page 2: ...es mises en danger Respecter scrupuleusement les indica tions de s curit Attention Instruction pour viter une possible mise en danger d appareils Prudence Instruction pour viter une possible mise en d...

Page 3: ...les mains ou les v te ments peuvent tre happ s par l entra nement par courroies ou par l accouplement Possibilit de graves blessures Absolument s curiser la zone de l accouplement par une grille de pr...

Page 4: ...ion excessive et aussi temp rature du gaz de refoulement augment e Avertissement En cas d introduction d air disloca tion critique de la limite d inflamma bilit de fluide frigorig ne Eviter absolument...

Page 5: ...ng foundation or vibration dampers If vibration dampers with single point support are used a reinforced frame construction may be necessary Motor compressor units with a cou pling housing see also cha...

Page 6: ...Les cheveux les mains ou les v te ments peuvent tre happ s par l entra nement par courroies ou par l accouplement Possibilit de graves blessures Absolument s curiser la zone de l accouplement par une...

Page 7: ...deflection are maintained approx values based on standard belt lengths 2 cylinder 9 11 mm 4 cylinder up to 4 N 2 11 12 mm 4 cylinder up to 4 G 2 15 17 mm 6 cylinder 13 15 mm The belt tension must be...

Page 8: ...r soigneusement les surfa ces de contact du compresseur du moteur et de la cage d accouplement 2 Fixer de la cage d accouplement au compresseur figure 5 Compresseurs 2T 2 Y 4N 2 Y W2TA W4NA Fixer la c...

Page 9: ...bserving the position of the coupling and screw together With type I subsequently bring the motor side coupling half into the correct position gap between coupling halves 2 3 mm and screw firmly to th...

Page 10: ...ap max 0 25 mm Attention Faulty alignement causes pre mature failure of the coupling and damage to bearings and the shaft seal Align motor shaft and com pressor shaft very carefully Attention The fixi...

Page 11: ...ng If not required the end with the largest diameter can be cut off Attention Do not overheat the valves Cool valve body while and after brazing Max brazing temperature 700 C 3 5 Raccordements de tuya...

Page 12: ...ation requis et la stabilit chimique du cir cuit 3 6 D marrage vide SU et R gulation de puissance CR Les parties sup rieures des vannes sont livr es s par ment afin d viter des d t riorations durant l...

Page 13: ...FA 1x 66 2x 33 66 residual capacity Retrofit requires exchange of the cylinder head For further explications see Technical Informations KT 100 and KT 110 D marrage vide SU Option pour tous les types E...

Page 14: ...N P T F 1 2 7 1 6 2 0 U N F 7 1 6 2 0 U N F 1 1 1 8 2 7 N P T F 1 H P 1 8 2 7 N P T F 1 8 2 7 N P T F 2 H P 3 L P 1 8 1 3 G 3 4 1 4 1 8 N P T F P a s s f e d e r P a r a l l e l k e y C l a v e t t e...

Page 15: ...as temp sensor HP 3 Low pressure connection LP 5 Oil fill plug 6 Oil drain magnetic screw 7 Oil filter 8 Oil return oil separator only for 2T 2 Y 6F 2 Y 8 Oil return with NH3 and insoluble oil only fo...

Page 16: ...dications de tension et de fr quence sur la plaque signal ti que avec les donn es du r seau Le moteur ne peut tre raccord que s il y a concordance Raccorder les bornes du moteur con form ment aux inst...

Page 17: ...be fit ted to the HP connection 2 see pages 14 15 For compressors with integrated start unloading the sensor must be fitted into the start unloading cylin der head see figure 10 The protection device...

Page 18: ...ord de service de la vanne d arr t R sistance de carter garantit le pouvoir lubrifiant de l huile m me apr s des longues p riodes stationnaires Elle permet d viter un enri chissement de l huile en flu...

Page 19: ...shift of the refrigerant ignition limit with high pressure possible Environmental pollution with leakage or when deflating 5 1 Strength pressure test Evaluate the refrigerant circuit as sembly accord...

Page 20: ...vide Mettre la r sistance de carter en service Ouvrir les vannes d isolement et les vannes magn tiques existantes Proc der la mise sous vide de l ensemble du syst me y compris le compresseur l aspirat...

Page 21: ...suction side while the compressor is in operation Charge preferably at the evaporator inlet Blends must be take from the charging cylinder as solid liquid If liquid is charged Attention Danger of wet...

Page 22: ...indiqu e sur le voyant Temp rature d huile environ 15 20 K au dessus de la temp ambiante resp temp de vapeur satur e l aspiration R glage et fonction des dispositifs de s curit et de protection R gla...

Page 23: ...ion Keep the discharge temperature at least 30 K R22 or at least 20 K R134a R404A R507A above condensing tem perature If larger quantities of oil have to be added Attention Danger of liquid slugging C...

Page 24: ...ts par manque de lubrification Fonctionnement du d tendeur se conformer aux indications du fabricant Position et fixation correctes du bulbe sur la conduite d aspiration En pr sence d un changeur de c...

Page 25: ...omer elements of the coupling again after running in period Check electrical cable connections on tight fitting Tightening torques see KW 100 Refrigerant charge tightness test Update data protocol Int...

Page 26: ...cas d une usure importante ou de diminution de section par cok faction de l huile ou la suite d une d t rioration des si ges des clapets Au cours du montage de la plaque clapets il faut prendre soin l...

Page 27: ...r and magnetic plug After that the oil has to be replaced approx every 3 years or 10 12 000 operating hours Clean also oil filter and magnetic plug NH3 plants Replace the oil yearly or after 5000 hour...

Page 28: ...s vannes d arr t du compres seur Aspirer le fluide frigorig ne Ne pas laisser le fluide frigorig ne s chapper mais recycler le de fa on adapt e Avertissement Le compresseur peut tre sous pression Grav...