Technical Data

Manufacturer:

Bircher Reglomat AG, Wiesengasse 20, CH-8222 Beringen

Authorised rep:

Bircher Reglomat GmbH, Robert Bosch Strasse 3, D-71088 Holzgerlingen

Following directives have been observed:

Manchinery directive 2006/42/EC, RoHS-Directive 2011/65/EU,

Low Voltage Directive 2006/95/CE until 19.04.2016, Low Voltage Directive 2014/35/EU starting 20.04.2016

EMC-Directive 2004/108/EC until 19.04.2016, EMC-Directive 2014/30/EU starting 20.04.2016

EC type-examination certi

fi

cate:

In combination with Safety Edges

Noti

fi

ed inspection centre:

Suva, Bereich Technik, SCESp 008, Kenn-Nr.1246

Signed:

Head of Sales & Marketing Damian Grand / Head of Operations Daniel Nef

Product variants:

ESR11-24VACDC, ESR11-230VAC, ESR12-24VACDC, ESR12-230VAC

Identi

fi

cation of the year of manufacture

Contact

EC-Declaration of Conformity

Bircher Reglomat AG

Wiesengasse 20

CH-8222 Beringen

www.bircher-reglomat.com

Year Month Day

2015 06 

05

Rights reserved for technical modi

fi

cations

Warranty and liability

1.   The warranty and liability of Bircher Reglomat AG are based on the sales contract.

2.   The warranty and liability shall expire prematurely, should the client or third parties not 

use and/or operate the product in compliance with existing operating instructions, should 

incorrect changes or repairs be made by the client or third parties, should the client or 

third parties, when a fault has occurred, not take suitable steps at once for a reduction of 

possible damage/losses and offer Bircher Reglomat AG a chance for remedying the said 

fault.

3.   The warranty and liability shall exclude any damage for which there is no proof that it is 

due to poor materials, faulty construction, poor workmanship, and any damage caused by 

other reasons, for which Bircher Reglomat AG cannot be held liable.

4.   No liability can be assumed for any consequential damage, provided this is not governed 

otherwise by applicable product liability laws and regulations.

5.   Warranty claims made against the seller on the basis of the sales agreement are not 

affected by these regulations.

6.   For the bene

fi

t of its customers Bircher Reglomat AG constantly develops its products 

further. Bircher Reglomat AG reserves the right to make changes to any of the products 

described in this document without prior notice.

Housing

Type M3, Material orange Noryl

Isolation Class

IP 30 (IEC 529)

Weight 

max. 250 g (depending on type)

– Type ESR-1. – 24 VADC

– Type ESR-1. – 115 VAC 

– Type ESR-1. – 230 VAC

24–36 VAC/24–48 VDC (±20%)

(+10/–20%) with isolating transformer

(+10/–20%) with isolating transformer

Frequency Range 

50/60 Hz (45 to 66 Hz)

Power consumption

max. 3 VA

Duty Cycle 

100%

Sensor Inputs

max. allowable voltage 15 VDC

max. allowable current 5 mA

Output relay/Error Indication Relay

– Switching Capacity

– Contact material

– Operating Life Mechanical

– Operating Life Electrical

– Fuse Protection

250 VAC/6 A (resistive)

Hard silver

30 million operations

80’000 switchings at 250VAC/6A resistive

6A slow-blow

Indicators

– Operation

– Safety Function

– Sensor Error

LED 5 mm

Green

Yellow

Red

Reaction Time 

< 70 ms

Temperature Range

– Operation

– Storage 

–20°C to +50°C

–20°C to +80°C

Humidity

max. 80% relative

Dimension sheet

ESR-13

Usage similar to ESR-11 however an additional error indication contact 

allows an external evaluation of the interrupted sensor input.

F1

P

N

Error

Indcation

ESR-13: 

 Error Indication Relay 
contacts open when error

ESR-13M:   Error Indication Relay 

contacts closed when error

Error collecting 

loop

F2

M

Sensor 
1

22(5)
32(8)

14(3)
12(4)
11(1)
31(11)

21(6)

F

S

F

S

24(7)
34(9)

A1(2)

A2(10)

Sensor 
2

74

36

12

85

Installation/Commissioning

a.   With the unit unplugged, check the sensor inputs 5/8 and 7/9 for the cor-

rect resistance value. This value should be between 7.5 kOhm and 

9 kOhm. If only one sensor is connected, the internal jumper must be 

fi

tted 

accordingly.

b.   Check the voltage information indicated on the unit type plate with that of 

the supply voltage.

c.   After switching on the unit, the green LED «Operation» illuminates. The 

yellow and red LED’s must not illuminate.

d.  The functioning of the system can be checked by the activation of a 

sensor. The LED of the corresponding input channel must illuminate. 

Periodic Tests

The correct function of the safety system is to be periodically checked 

(e.g. monthly or according to applicable regulations). The sensors and their 

connections are to be inspected to determine possible mechanical damage. 

In addition, the sensor wiring should be disconnected annually and checked 

as described in Commissioning points a. and c.

Trouble Shooting

Initial Position:

– Connections according to wiring diagram

1.   Green LED does not illuminate

  Check the power supply. If the voltage is correct the unit is defect.

2.   Yellow LED illuminates even though the sensor is not activated Switch off 

power supply and remove unit. Measure resistance values at terminals 

5/8 and 7/9. The resistance value must be between 7.5 kOhm and 

9.0 kOhm. If the values are lower, the sensor and the connections must be 

checked for any eventual short circuit.

3.   Red LED illuminates

      Repeat procedure under point 2. If the resistance values are correct the 

unit is defect.