BINMASTER SBRX AO Operating Instructions Manual Download Page 1

SmartBob AO

OPERATING INSTRUCTIONS

PLEASE READ CAREFULLY

BinMaster: Division of Garner Industries

7201 N. 98th St., Lincoln, NE 68507

402-434-9102 • email: [email protected]

www.binmaster.com

925-0406

0613

Summary of Contents for SBRX AO

Page 1: ...SmartBob AO OPERATING INSTRUCTIONS PLEASE READ CAREFULLY BinMaster Division of Garner Industries 7201 N 98th St Lincoln NE 68507 402 434 9102 email info binmaster com www binmaster com 925 0406 0613...

Page 2: ...4 20 mA Output 8 Relay 1 and 2 Outputs 9 Wiring Diagram 10 Air Purge System 11 User Interface 11 Run Display Mode 12 Setup Menu 12 Calibrating the 4 20 mA Output 14 Motor Driven Operations 14 Cable Re...

Page 3: ...ng normal operation If this product is used in a manner not specified by the manufacturer the safety protection could be compromised Safety Terms and Symbols WARNING Warning statements identify condit...

Page 4: ...ncoder counts are compared to determine the distance to product The distance to product measurement is then used to update a display and a 4 20 mA current transmitter The display simply shows the meas...

Page 5: ...e external power required Mode 2 Non isolated SmartBob AO powers the loop Max Loop Resistance Mode 1 Depends on external power Max Loop Resistance Mode 2 500 ohms Accuracy 0 35 Resolution 16 bits maxi...

Page 6: ...according to local and or national codes and have a tem perature rating of at least 85 C All wiring and jumper configuration should be made with AC power removed Power A disconnecting means should be...

Page 7: ...a connection to this input Override Input This input is used to prohibit measurements from occurring and should only be connected to a normally closed set of dry contacts Whenever the contacts connect...

Page 8: ...le between 14 and 20 AWG will work for a connection to this input Mode 1 provides for electrical isolation up to 3 750 Vrms In this mode the SmartBob electronics are isolated from the on board 4 20 mA...

Page 9: ...here are two user configurable normally open relay outputs available for signaling a high level alarm a low level alarm an error alarm or a measurement indication When set for a level alarm the relay...

Page 10: ...t These relays can switch low current signals and are not meant to power motors or high wattage light bulbs Be sure to read the voltage and current limitations in the Specification sections An unshiel...

Page 11: ...s prevented from entering into the unit The external pressure should be one 1 psi greater than the ambient pressure in the storage vessel and should be free from moisture and other contaminates User I...

Page 12: ...easurement or other motor driven operation Once in the setup menu measurements and other motor operations will not occur Use UP DN keys to change the displayed setting Hold the key for repeated adjust...

Page 13: ...fault is 0 00 feet Maximum Drop Distance This is the maximum distance the SmartBob AO will allow the bob to drop which can range from 0 34 to 409 59 feet or 0 11 to 124 84 meters The default is 60 00...

Page 14: ...ld provide 20 mA output In this case simply set the 4 mA drop distance to 0 50 feet and the 20 mA drop distance to 6 00 feet Any mea surement of 6 0 feet or more empty will drive the output to 20 mA a...

Page 15: ...upply Pulley 4 After loading the supply pulley skip to Threading the Cable Kit Replacement 1 Loosen the 1 4 set screw located on the hub of the supply pulley then remove the supply pulley assembly 2 R...

Page 16: ...Load supply pulley by pressing the UP button located on the circuit board Pressing this button will start the supply pulley turning in a clockwise direction with the cable winding over the top Keep th...

Page 17: ...rsion is order code B2 B3 This probe is a hollow inverted 4 inch cone made of stainless steel and is designed for bulk products with a density from 5 lb to 20 lb per cubic foot This probe should not b...

Page 18: ...e bottle is made from an engineering plastic which will not damage the material handling auger in the unlikely event that the probe should become separated from the unit Order code B6 is an empty bott...

Page 19: ...Hold the cable tight so it cannot rewind The motor should now be shut off 2 From the throat or pipe extension of the SmartBob AO measure the height of your vessel or the maximum distance you want the...

Page 20: ...925 0406 0613 SmartBob AO Mounting Options Standard Flange Mount High Temperature Mount...

Page 21: ...0613 925 0406 SmartBob AO SMARTBOB REMOTE MOUNTING TEMPLATE 5 inch floor flange...

Page 22: ...925 0406 0613 SmartBob AO SMARTBOB REMOTE MOUNTING TEMPLATE 5 inch floor flange...

Page 23: ...em in the order as shown in the figure below 1 Ball Stop 2 Round Crimp 3 Ball Stop 4 Round Crimp 5 Cap 6 Ball Stop 7 Oval Crimp 8 Thimble 9 Cable After all items are located as shown compress the crim...